OPERATIONEATON Powerware® 9140 UPS (7.5–10 kVA) User’s Guide S 164201622 Rev A FINAL DRAFT 14-Jul-200658The following table shows the indicator status and description.Indicator Status DescriptionOn The UPS is operating normally.Green Slow Flash The UPS is in Standby mode.Fast Flash The UPS is starting up.Off The UPS is turned off and will not turn on automatically.On The UPS is in Battery mode.Yellow Slow Flash The UPS is in Battery mode and a Low Battery condition is detected.YellowFast Flash A battery test is in progress.On The UPS is in Bypass mode.Yellow Slow Flash Bypass mode in unavailable because the input utility is outside the configuredbypass range.On The UPS has an active critical alarm and is not supporting the load.See “Troubleshooting” on page 89 for additional information.Red Slow Flash The UPS has an active warning alarm and is supporting the load.See “Troubleshooting” on page 89 for additional information.All LEDs Slow Flash The UPS is powering down and the load is no longer supported.Cycling A UPS flash upgrade is in progress.Changing the LanguageTo change the language setting, select MENU from the system statusscreen, then select SETUP, USER SETUP, and LANGUAGE. Scrollthrough the available options and press the button to select thelanguage.