POWER WIRING INSTALLATION NOTES071608D19 of 23DESCRIPTION:DATE:DRAWING NO: SHEET:REVISION:164201603-5INSTALLATION INFORMATIONEATON Powerware® 9390 UPS (20–80 kVA) Installation and Operation Manual 164201603 Rev 2 www.powerware.com A-29Table S. INPUT/OUTPUT Ratings for Powerware 9390-40/20, 9390-40/30, 9390-40/40 and9390-80/40 Parallel SystemsConfiguration Units Rating 50/60 HzBasic Unit Rating at 0.9 lagging pF load kVAkW40364036403640364036Input and Bypass InputOutputVOLTSVOLTS208/220208/220380380400400415415480480AllAC Input from UPMFull Load Current for each Module(3) Phases, (1) Neutral, (1) Ground DAmps 111/105 62 58 56 48Minimum Conductor Size for each ModuleNumber per Phase for each ModuleAWG or kcmil(each)See Table G through Table J for wiresize.1+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 111/105 62 58 56 48AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral, (1) GroundG Amps 111/105 62 58 56 48System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 28)- AWG or kcmil(each)6(1)8(1)8(1)8(1)8(1)2+0and2+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 222/210 124 116 112 96AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral, (1) GroundG Amps 222/210 124 116 112 96System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 28)- AWG or kcmil(each)2(1)4(1)4(1)4(1)6(1)3+0and3+1AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 333/315 186 174 168 144AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral, (1) GroundG Amps 333/315 186 174 168 144System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 28)- AWG or kcmil(each)1/0(1)2(1)2(1)2(1)4(1)4+0AC Input to Tie Cabinet Bypass (optional)Full Load Current(3) Phases, (1) Neutral-if required, (1) GroundF Amps 444/420 248 232 224 192AC Output to Critical LoadFull Load Current(3) Phases, (1) Neutral, (1) GroundG Amps 444/420 248 232 224 192System Neutral Bonding JumperMinimum Conductor SizeNumber (See Note 28)- AWG or kcmil(each)2/0(1)1/0(1)1/0(1)1/0(1)1/0(1)NOTE Callout letters D, F, and G map to Drawing 164201603-4, sheets 3 of 5, 4 of 5,and 5 of 5.