UPS OPERATING INSTRUCTIONSEATON Eaton 9395 550/275 UPS (225–550 kVA) Installation and Operation Manual 164201716 Rev 2 www.eaton.com/powerquality7-327.4.3 Disable Energy Saver System Mode from the UPS Command MenuTo disable Energy Saver System mode:NOTE The Energy Saver System mode commands are displayed only if enabled at the factory or by anEaton Customer Service Engineer.NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.If the Variable Module Management System mode is enabled, the Energy Saver System mode commands willnot be displayed.1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the UPS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The UPSControl Command screen is displayed.4. On the UPS Control Command screen, select DISABLE ENERGY SAVER.5. Press the SELECT pushbutton on the UPS Command menu bar.The UPS transfers to Battery mode and then to Online mode.The Online status indicator is illuminated. The UPS status indicates ONLINE. TheUPM status indicates ONLINE.7.4.4 Start Energy Saver System High Alert Mode from the UPS CommandMenuTo start High Alert mode:NOTE The High Alert mode commands are displayed only if enabled at the factory or by an Eaton CustomerService Engineer.NOTE The Variable Module Management System and Energy Saver System modes are mutually exclusive.If the Variable Module Management System mode is enabled, the Energy Saver System mode commands willnot be displayed.1. Press the CONTROLS pushbutton on the main menu bar. The System Statusscreen is displayed.2. On the System Status screen, select the UPS command.3. Press the CONTROLS pushbutton on the System Status menu bar. The UPSControl Command screen is displayed.4. On the UPS Control Command screen, select START HIGH ALERT.5. Press the SELECT pushbutton on the UPS Command menu bar.The UPS starts High Alert mode with the UPMs online supplying the critical load.After one hour the UPS transfers to Energy Saver System mode.The Online status indicator is illuminated. The UPS status indicates HIGHALERT. The UPM status indicates ONLINE. The power module is on.