UPS STARTUPEaton FERRUPS Rack Mount UPS (850 VA–7 kVA) User's Guide 164201424 Rev 1www.eaton.com/powerquality205. For Plug-Receptacle UPSs: Plug the equipment to be protectedinto the UPS output receptacles.NOTE For 50-Hz models, use the supplied IEC-320 jumper cord to connect your equipmentto the UPS output receptacles.For Hardwired UPSs: Turn the bypass switch to the UPS position.6. Turn on the equipment that is connected to the UPS.If the ALARM indicator illuminates, see “Alarms” on page 61.7. If your FERRUPS Rack Mount UPS is configured to use an externalbattery cabinet, you must program the battery capacity inampere-hour (Ah) for the total number of battery packs used in theUPS. If you purchased one of the FERRUPS Rack Mount batterypack options available from Eaton, select the Ah value from Table 1.NOTE A Remote Control Panel (part number RCK-0007), PC, or terminal is required tocommunicate with the UPS.Before programming the battery Ah, enter the user-level passwordfollowing the instructions in “Entering Passwords” on page 30. Tochange the battery Ah, parameter 69 (Batt Ah), follow these steps:Press this key: Display shows:[DISPLAY] [6] [9] [ENTER] 69 Batt AH [Default][PROGRAM] 69 Pgm:[Ah Value from Table 1] 69 Pgm: [xxx][ENTER] 69 Pgm: [new value]where xxx is the Battery Ah value from Table 1.