Pub 49440Effective 01/02 5Figure 12. Adjust Time and TorqueHow to Adjust Time and Torque, Figure 12Control of the motor torque is achieved by acting on the motorvoltage.The motor speed depends on the torque produced bythe motor and the load on the motor shaft. A motor with little orno load will reach full speed before the voltage has reached itsmaximum value.NOTE: The soft start controller will read time and torque set-tings in the OFF state. Repeated starts may trip themotor protection relay. DO NOT set the rotaryswitches in between positions. This corrupts the timeand torque adjustment. Use screwdriver 2 mm x0.5 mm.Rating IndexTable 8. Rating IndexRamp-Up Time and Initial TorqueTable 9. Ramp-Up Time and Initial Torque(Standard Load)Kick Start/Break LooseIf it is not possible to reach a time sufficient for the application,it may be necessary to kick start the load.Table 10. Kick Start/Break Loose (High Inertia Loads)Ramp-Down TimeFollow Table 9 to set Ramp-Up and Initial Torque.Table 11. Ramp-Down Time, e.g. Pump Loads200ms kick start withAdj. Torque, 0 - 85%0100%Motor VoltageTimeRamp-Up, 0.5 - 10 Sec.Ramp-Down, 0.5 - 10 Sec.Torque Adjustment, 0 - 85%8,25,63,90,81,21,802,78,25,63,90,81,21,802,7JtRamp upUtRamp downUtInitial torqueUtKick start04664202642 02604A1 A22 /T1 4/T2 6/T311 121/L1 3 /L2 5/L3S701E25N3S92EQ10005A0001AS701_15N3S S701_25N3S15A: AC-52a: 4-13 : 100 – 3000 25A: AC-52a: 4-13 : 100 – 300015A: AC-53a: 8-3 : 100 – 3000 25A: AC-53a: 8-3 : 100 – 300015A: AC-58a: 6-6 : 100 – 3000 25A: AC-58a: 6-6 : 100 – 3000Position Setting/AdjustmentSet the Ramp-Up switch to maximum.Set the Ramp-Down switch to minimum.Set the Initial Torque switch to minimum.Apply control signal for a few seconds. If the load does notrotate immediately, increment the Initial Torque and tryagain. Repeat until the load starts to rotate immediately onstartup.Adjust Ramp-Up time to the estimated start time (thescale is in seconds) and start the motor.Decrease the Ramp-Up time until mechanical surge isobserved during start.Increase the time one step to eliminate the surge.8,2 000Position Setting/AdjustmentSet the Ramp-Up switch to maximum.Set the Ramp-Down switch to minimum.Set the Initial Torque switch to minimum kickstart torque.Apply control signal for a few seconds. If the load stopsright after the 200ms “kick”, increment the Initial Torqueand try again. Repeat until the load continues to rotateafter the “kick”.Adjust Ramp-Up time to the desired start time (the scale isin seconds) and start the motor.Position Setting/AdjustmentSet the Ramp-Down switch to maximum.Switch off the control voltage and observe any mechanicalsurges on the load. If there are none, decrement Ramp-Down switch and try again. Repeat until mechanical surgeon the load is observed.Increase the time one step to eliminate the surge.8,2 0008,2 00