Installation10 Eaton T2235 Series eATS ePDUs P-164000014—Rev 1 www.eaton.com/ePDUKIT-CABLRES-03 Universal Cable Restraint SystemThe following parts for installing the optional cable restraint tray are located in the KIT-CABLRES-03 shippingcarton:l (1) Cable management tray (001-2211-2)l (2) Mounting brackets (001-2233-2)l (11) 6-32 X 1/4” black screws (035-1606)l (12) Tie-wraps, 8” (010-0008)Before You InstallConsider where you will locate the T2235 Series eATS ePDU model. These models are typically mounted atthe bottom or rear of the equipment cabinet. This location is convenient because heavy power cables areusually routed at the bottom of the cabinet.Ensure that you select a location with proper spacing. The T2235 Series eATS ePDUs typically require 44.5 mm(1.75”) of vertical mounting space and extend 177.8 mm to 241.3 mm (7–9.5”) into the mounting rack of thecabinet. Eaton recommends mounting the ePDU as close as possible to the equipment it controls.Determine if you need additional weight support. The ePDU is designed to support its own weight only. Eatonrecommends using cable management and support brackets, such as the KIT-CABLRES-01 Universal CableRestraint System.Consider temperature specifications in the installation site. Ambient temperature at the installation site shouldnot exceed 35°C (95°F). Relative humidity should remain below 95%, noncondensing.CAUTIONThe ePDU uses unpainted mounting brackets that serve as grounding to the rack. No separateground connection is necessary. For proper grounding, the electrical connection between theT2235 Series eATS ePDU and the cabinet or rack must be secure.Installing Optional Mounting HardwareFor T2235 Series eATS ePDU models, optional mounting hardware is available, including attachable cablerestraint trays.Cable Restraint TrayTo install the cable restraint tray:1. Place the ePDU on a flat, stable surface.2. Slide the cable restraint tray onto the ePDU. Align the holes in the tray bracket with the screw holes onthe ePDU.3. Secure the cable restraint tray to the ePDU with the tray mounting screws (supplied).4. Secure the ePDU with attached cable restraint tray to the rack rails with the ePDU mounting screws(supplied).5. This procedure is completed.