6 XC-152 as a SmartWire-DT coordinator6.1 SmartWire-DT operator control and display elements60 Compact PLC XC-152 05/17 MN050001ZU EN www.eaton.com6.1.1 POW/AUX SWD power supplyThis connection ensures that the power required for the SmartWire-DT net-work will be supplied.Characteristics: WAGO connector, 4-pole, not galvanically isolatedThe following power supplies are required for a SmartWire-DT network:• POW supply voltage:The device supply voltage for the electronics in the downstream SWD-modules (15 VDC) is generated using the 24 VDC supply voltage appliedat the POW terminal.• AUX supply voltage:If there are any contactors or motor starters in the SWD- topology, a 24VDC AUX voltage must be additionally supplied as a control voltage forthe contactor coils..Operator control and displayelements for SmartWire-DTDescriptionabcdPOW/AUXSWD power supplyPower supply for the SmartWire-DT networka +24 V DC POW, b 0 V DC POW, c +24 V DC AUX,d 0 V DC AUXe POW-LED Lights up when the SmartWire-DT network is powered.f SWD-LED Indicates whether the physical configuration of the SmartWire-DTnetwork matches the target configuration stored in the device.The configurations will be compared with each other every time thepower is switched on.g Config-LED Indicates whether the SWD master project configuration defined in thePLC matches the SmartWire-DT network target configuration stored inthe device. The configurations will be compared with each other everytime the power is switched on.h SWD Interface SmartWire-DT ribbon cable connectioni Configconfiguration buttonUsed to configure the SmartWire-DT network.→ If contactors and/or motor starters with a total current draw > 3A (DIN VDE 0641, Part 11 and IEC/EN 60898) or > 2 A (UL 508and CSA-22.2, No. 14) are connected, an EU5C-SWD-PF1 orEU5C-SWD-PF2 power feeder module needs to be used.→ If SmartWire-DT modules with a total current draw > 0.7 A areconnected, an EU5C-SWD-PF2-1 power feeder module needsto be used.