5 Installation5.2 Requirements for the place of installation26 MICRO PANEL XV400 10.4"/12.1"/15" 12/2010 MN04802010Z-EN www.eaton.com5.2 Requirements for the place of installation Approvals:The device must only be used in locations that are approved for the device. See the markings onthe nameplate and Chapter 9 Technical data, 67. Power supply:The power supply must comply with the requirements stated in Chapter 9.5.1 Power supply, 75.5.2.1 Requirements for use in EX Zone 1 and 2The following requirements must be fulfilled in order for a device to be used in EX Zone 1 and 2: The device must have a stainless steel front. The device must be mounted in a pressurized housing that has an EC type certificate for Ex px(pressurized enclosure). The device is mounted with the sealing strip and eight retaining brackets (supplied). Ambient temperature range: 0°C ≤ Ta ≤ +50°C(maximum surface temperatures: front 70°C / electronics 110°C) Max. permissible pressure: 10 mbar continuous and during rinsing 30 mbar All instructions in this document must be observed.5.2.2 Engineering conditions of acceptability by Underwriters Labaratories Inc. (UL)The device must be installed in an end-product. Consideration must be given to the following: The environment of the device must comply with pollution degree 2. The device must be supplied via a SELV source. The device must be connected to the protective earth of the end-product (the functional earthingconnection of the power supply interface must be connected). In order to protect the device from potential internet threats, it should be connected to Ethernetnetworks that are isolated from the internet or safety protected and isolated from the Corpo-rate/Enterprise network by a firewall or router. Fire protection and electrical protection must be ensured via the end-product (not required for thefront of the device).5.2.3 Requirements for the mounting positionThe device is designed for mounting in control cabinets, control panels or control desks. 10.4" and 12.1"devices can be mounted horizontally or vertically, 15" devices must only be mounted horizontally. Thefollowing requirements must be fulfilled when selecting a suitable mounting position: The display should not be exposed to direct sunlight (the UV component of sunlight reduces thelifespan of the device and disturbs the infra-red touch sensor). If the device is to be used in potentially explosive atmospheres, the device must not be subjectedto hazardous knocks. The operating elements on the service side of the device and the cable connections are accessibleafter the device has been mounted. The ambient conditions stated must be observed. See Chapter 9.9 Ambient conditions, 79. Sufficient ventilation (cooling) must be ensured by means of: Clearance of at least 3 cm to the ventilation slots