IM0217.Revision 5 05/17 Page 1 of 34. Conformity with standardsThis explosion protection floodlight meet the requirements of IEC/EN 60079-0,IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-18, IEC/EN 60079-31. It also complieswith the EC Directives for “Apparatus and protective system for use in explosionatmospheres” (2014/34/EU). It has been designed, manufactured and tested inaccordance to the state of the art and according to ISO 9001:2000. The luminairesare suitable for use in explosive atmospheres, Zone1,Zone2 according to IEC60079-10-1 and dust area Zone21 and Zone22 according to IEC60079-10-2.5. Fields of ApplicationThe ATEX category 2 GD Luminaire with a separate Exe terminal box utilizes Ex demprotection and IP66 sealing making it suitable for use for potentially explosiveatmospheres including ignitable gas and dust applications.The luminaire is designed for use in Zone1/Zone21 and Zone2/Zone22 hazardousareas in indoors and outdoors in Marine and Wet locations, where moisture, dirt,corrosion, vibration and rough usage may be present. Application ambienttemperature is -40ºC~+40/45/50ºC for different version. Refer to the luminairenameplate, For specific information, corresponding operating temperature(T-Code).The enclosure materials used, including any external metal parts, are High qualitymaterials that ensure a corrosion resistance and resistance to chemical substancesaccording to the requirements for use in a “normal“ industrial atmosphere. In caseof use in an extremely aggressive atmospheres, please refer to manufacture.3. Safety InstructionsThis product should be installed, inspected, and maintained by a qualifiedelectrician only, in accordance with national regulation, including the relevantstandard and, where applicable, in acc. With IEC/EN 60079-17 on electricalapparatus for explosive atmospheres. The national safety rules and regulationsfor prevention of accidents and the following safety instructions in theseoperating instructions, will have to be observed!The luminaire must not be operated in Zone0 and in Zone20!When using in Zone21,Zone22, the requirements of IEC/EN 60079-14 relating totemperature must be observed. The indicated surface temperatures in table 7are not related to a layers above 5 mm thickness.Do not install where the marked operating temperature exceed the ignitiontemperature of the hazardous atmosphere.Do not operate in ambient temperatures above those indicated on theluminaire nameplate.The luminaires shall be operated as intended and only in undamaged andperfect conditions! And Keep tightly closed when in operation!The technical data indicated on the luminaire are to be observed!Change of the design and modifications to the luminaire are not permitted!Multiple, short-term switching must be observed!Only genuine Cooper Crouse-Hinds spare parts may be used for replacement!Repairs that affect the explosion protection, may only be carried out byCooper Crouse-Hinds or qualified electrician!!1. Dimensions Normal version/Indirect entryEM version/Indirect entry EM versionDirect entry2. Technical dataHazardous area specificationType of protection: Ex d e m & Dust protected enclosureATEX classification: Group II Category 2 G DCertification Marking: II2 G Ex db e mb op is IIC T6 GbII2 D Ex tb IIIC T80ºC Db IP66Ambient temperature: -40ºC~+40ºC/45 ºC/50ºCTemperature class: Refer to Type configurationEC type examinationCertification No.: EPT 16ATEX 2405IECEx Certificate No.: IECEx CQM 15.0054XDegree of protection: IP 66 acc. to EN60529/IEC60529Approval of the productionQuality assurance: Baseefa ATEX 5952Enclosure specificationMaterial of enclosure: Aluminum alloy without CuFinish: Painted polyester power coatingMaterial of globe: Tempered glassMounting bracket: Stainless steel or Steel paintedFasteners: All external fasteners stainless steelInstallation: Mounting bracket with aiming quadrantWeight: Refer to Type Configuration.Entry specificationIndirect entry: M20×1.5 or M25×1.5 cable entry. One entry is fittedwith an Exe stopping plug. Direct entry: Exd M25×1.5 cable entry.Electrical specificationWattage: 25W~80WVoltage: AC: 100V-240V 50/60Hz, DC: 108~250VLamp: LED ArraysCRI: 70Insulation class: I acc. to IEC60598Terminals capacity: 3 core or 6 core conductor/cableSolid: 0.5~6mm2, Flexible: 0.25~4mm26. Cable gland recommendEntry size Part No. Cable sizeTorque (Nm)screw-in enclosure For cableM20 CAP816609 8.5-16 20 20M25 CAP816709 12-21 30 30M25 CCL0803086 12-15 25 42Note: Mounting the selected cable glands acc. type and dimensions ofthe main connection cable. Following their manufacturer instructions.Normal versionDirect entry