www.fanox.com Rev.26 111/1885.13.2. SIA-C withdrawable modelIn this item it is developed the situation of trip onto fault of SIAC11500032AFA (withdrawablemodel)This relay is operative with 0.2 times the secondary rated single-phase current and with 0.1times the secondary rated three-phase current; in other words, the equipment powers itselfwith 200 mA of single-phase current and with 100 mA of three-phase current.0,2 A 0,5 A 1 A 2 A 5 A 8 A 10 A 20 A 30 A 40 A 50 ATime (ms) FAST & 1 PHASE 1200 300 180 120 110 105 105 105 105 105 105020040060080010001200Tripping time (ms)x InSIA-C1