www.fanox.com Rev. 26 58/1883.4. Selection & Ordering dataSIA C PROTECTION FUNCTIONS50P + 50/51P + 50N/G + 50/51N/G + 86 + PLC15PHASE MEASUREMENTIn = 1 A; (0,10 – 30,00 A)In = 5 A; (0,50 – 150,00 A)15ABNEUTRAL MEASUREMENTIn = 1 A; (0,10 – 30,00 A)In = 5 A; (0,50 – 150,00 A)In = 0,1 A; (0,01 – 3,00 A)In = 0,2 A; (0,02 – 6,00 A)56NET FREQUENCY50 Hz60 Hz012345POWER SUPPLYSelf poweredSelf powered + 230 Vac (Dual)Self powered + 110 Vac (Dual)Self powered + 24 Vdc (Dual)Self powered + 48 Vdc (Dual)Self powered + 85-265 Vac-dc (Dual)01234ADDITIONAL FUNCTIONSStrikerStriker and with external trip (49T)CoilCoil and with external trip (49T)Striker and 230 Vac adapted external trip01COMMUNICATIONSLocal ModBus port (RS 232)+ Remote ModBus port (RS485)0123INPUTS-OUTPUTS-2 Outputs to signalling2 Outputs + 2 inputs3 Outputs to signalling12MEMORYNon-volatile RAM memoryNon-volatile RAM memory + Fast start-upABCDLANGUAGEEnglish, Spanish and GermanEnglish, Spanish and TurkishEnglish, Spanish and FrenchEnglish , Spanish and RussianABCDEFGMECHANICSVertical, withdrawable with 3 magnetic FlagsHorizontal assembly with 1 magnetic FlagHorizontal assembly with 3 magnetic FlagVertical assembly with 1 magnetic FlagVertical, Compact Size with 3 magnetic FlagVertical, Compact Size, 3 Flags, Backlight LCD, withdrawableVertical, Compact Size, 1 Flag, Backlight LCD-ABADAPTATION50P + 50/51P + 50N/G + 50/51N/G + 86 + PLC+ 50P_2 + 50N/G_2 + 3 Settings group+CLP + 4 Settings groups