LCD Display RepositioningWARNING: Refer the repositioning of the LCD display to a qualified electronic technician orthe Falcon Service Department. LIVE COMPONENTS ARE INSIDE THIS UPS ANDRISK OF ELECTRICAL SHOCK.Prior to anyone starting to attempt the repositioning of the LCD display, SERVICEPERSONNEL MUST FIRST disconnect the UPS line cord and power plug, removethe battery fuse located on the UPS rear panel, disconnect any external batterybanks and let the UPS discharge for one hour.The default LCD display mounting is for horizontal (Rackmount) viewing. To reorient the LCD displayfor vertical (Free Standing) viewing, remove the left half of the front plastic bezel by unscrewing thescrews to the far left of the chassis. Next, remove the four screws securing the right plastic paneland pull the right panel forward evenly. Refer to the following figure, unscrew the LCD board androtate it 90 degrees, to the correct position for viewing. Use care when handling the LCD display andassociated cabling. Mount the front covers back and reinstall the screws.SSG & HW Battery Bank Installation(SSG1.5KRM-X internal battery, SSG2.2KRM-X & SSG3KRM-X standard battery bank and all SSGextended battery banks)Note:Additional battery banks can be connected to the UPS to provide additional battery run time.There are two models of extended battery banks available for the SSG Series. Falcon model numberSSGR is a universal battery bank without an internal charger. It may be added to any SSG 1.5-3kVAmodels. For 2.2-3kVA models, the addition of this type of extended battery bank will cause the stat-ed recharge time to multiply by the number of battery banks added. The addition of more than threeSSGR battery banks is not recommended. Use the SSGR-1 model universal extended battery mod-els instead, as it incorporates internal battery chargers to assure proper battery recharging andgreatly reduces the amount of battery recharge time.13