NOTE!DURING SHUT DOWN, DO NOT PRESS ANY BUTTON SINCE UPS MIGHT BERE-ENERGIZED AND DELIVER POWER TO ITS OUTPUT UNEXPECTEDLY.6.0 UPS SETUP, CONFIGURATION & PROGRAMMINGThe following section describes how to reconfigure the internal UPS setup options, by using theSetup, Configuration & Programming Mode. The setup options include: The UPS output voltage,enabling or disabling Green Mode and output Segment Control operational mode settings.CAUTIONNever change the voltage settings when the UPS is ON and powering any connectedloads.How To Place the UPS Into Setup/Configuration ModeTo place the UPS into configuration mode: press the "Function/Test" and "Set/Alarm Silence" buttonsat same time and hold them for one second. The unit will emit one audible beep and display functionand status bit window at the bottom of the LCD display, entering Configuration Mode.Note on the bottom of the display panel, you will see a single row, 8 BITcolumn located at the bottom of the display. The right most bit is functionBIT 0, with the remaining seven bits to the left, function bits 1 through6. The last BIT 7 is the Status Bit and will indicate the setting status of theother Function bits. Repeat pressing of the "Function/Test" button will movethe dot from function BIT 0 (far right) to function BIT 6. When selectingfunction BIT 0 through BIT 6, observe whether status BIT 7 has a (Dot) or(No Dot) displayed for the function bit selected. To select a dot or no dotfor the function you are presently in, press the "Set/Alarm Silence" button toturn on (Dot) or turn off (No Dot) in status BIT 7. Next, press the“Set/Alarm Silence" and “Function/Test" buttons at same time, and hold forone second. The audible alarm will sound one short beep to acknowledgethe UPS has stored the selected settings.Setting the Green Mode Function (set to disabled from factory)Green Mode is a power saving feature that should only be used in non-critical applications when theconnected computer or equipment is the only device being protected by the UPS and when turnedoff, UPS battery backup is no longer necessary. When the Green Mode is enabled and the connect-ed load decreases to less than 3% of the full rated UPS output capacity, the UPS will automaticallyswitch from on-line to Bypass Mode, 30 seconds after the drop in load has been detected. After theUPS has switched to Bypass Mode, the Green Mode bulb icon will flash to indicate the UPS is in theenergy saving Green Mode. While in Green Mode, should the load increase to greater than 3% ofthe UPS's full output rating, the UPS will automatically return to normal On-line Mode operation.CAUTION- When Green Mode is enabled, and the UPS has switched to Bypass Mode due to areduction in load, THE UPS WILL NOT GO TO BATTERY MODE IN THE EVENT OF A UTILITYFAILURE. THE CONNECTED LOAD WILL BE TURNED OFF. Turning Green Mode off inconfiguration mode will restore normal UPS operation.20