©2010 Falcon ® Electric, Inc. All rights reserved. Falcon ® and the Falcon Electric logo are registered trademarks of Falcon Electric, Inc.All other brand names and trademarks are the property of their respective owners.The information and specifications stated in this document are subject to change without notice. 08-13-2010Falcon Electric, Inc. - 5106 Azusa Canyon Rd. - Irwindale, CA 91706 - 800.842.6940 Fax 626.962.7720www.falconups.com - email: sales@falconups.comSSG SeriesTM Industrial-Grade UPS PLUS®1.5kVA - 3kVA39Model Number SSG1.5KRM-1SSG1.5KRM-2SSG2.2KRM-1SSG2.2KRM-2SSG3KRM-1SSG3KRM-2Nominal VA 1500 2200 3000Electrical InputNominal AC Voltage -1 Models 120Vac-2 Models 208-240VacAC Voltage Range -1 Models 80-138Vac-2 Models 160-276VacFrequency 50/60 Hz ± 5% (Auto Tracking)Power Factor Correction > 0.97 (at full load)Surge Suppression IEEE/ANSI C62.41Efficiency (Typ.) > 87%Electrical OutputWatts 1050 1540 2100AC Voltage (User Programmable) -1 Models = 100, 110, 115 or 120Vac (sinewave)-2 Models = 208, 220, 230 or 240Vac (sinewave)Frequency 50/60 Hz (Auto Tracking or user programmable fixed 50 or 60Hz modes)Frequency Stability ± 0.3% (Battery Mode), ±5% Synchronized to the input frequency in utilitymodeVoltage Regulation ± 2%Step Load Change ± 7% for 100% load variation, recovery in 5msHarmonic Distortion < 3% Linear Load, < 5% Non-Linear LoadOverload 150% for 10 seconds, 110% for 20 seconds, 105% for 50 secondsCrest Ratio 3:1BatteryDC Bus Voltage (nominal) 48Vdc 96VdcBattery Pack Type User-Replaceable, Hot-Swappable (Batteries are replaceable through the front panel)(Battery packs are replaceable through the front panel without removing the UPS, battery bank or EBM from the equipment rack)Battery Type (With standard VRLA Type)SSGLi-4 Ten-Year Lithium-Ion Battery Option10-Year Rated, VRLA Batteries, 12Vdc, 7AH(4) 10-Year Rated, Lithium-Ion 12Vdc, 4.6AH10-Year Rated, Maintenance-Free, Sealed VRLA Batteries, 12Vdc, 7AHN/ABack Up Time (With standard VRLA Type)SSGLi-4 Ten-Year Lithium-Ion Battery OptionSSGLi-8 2U External Lithium-Ion Bank5 minutes / 16 minutes9.5 minutes / 20 minutes28.5 minutes / 60 minutes8 minutes / 20 minutesN/AN/A6 minutes / 18 minutesN/AN/ARecharge Time 8 Hours to 90%Transfer TimeLine Fails/Recovers ZeroUPS to Bypass or Reverse < 4msAfter Overload Auto Transfer to UPSWith Frequency Converter Options Bypass DisabledElectrical ConnectionsInput -1 Models = 6’ Cord with 5-15P Plug-2 Models = 6’ Cord with Schuko Plug-1 Models = 6’ Cord with 5-20P Plug-2 Models = 6’ Cord with Schuko Plug-1 Models = 6’ Cord with L5-30P Plug-2 Models = 6’ Cord with Schuko PlugOutput (8) 5-15R(4) IEC320(4) 5-15R & (1) L5-20R(4) IEC320(4) 5-15R & (1) L5-30R(4) IEC320EnvironmentalTemperature OperationalStorage-20ºC - 55ºC (-4ºF to 131ºF) (Extended operation in temperatures above 25ºC will shorten the battery life)-15ºC - 50ºC (5ºF to 122ºF) (Extended storage in temperatures above 25ºC will shorten the battery life)Humidity 10% to 95% Non – CondensingAltitude 10,000 Feet (3000 meters) without deratingCooling Low Velocity Forced Air FansHeat Dissipation (BTU/Hour) 535 784 1071Audible Noise (@ 1 Meter) <50dBAControls & IndicatorsLCD Display MIMIC Graphical Display, Input/Output Voltage, Frequency & Load, Alarm, Programmable settings & UPS state iconsAudible Alarms DC Mode, Low Battery, Over/Under Voltage, Over/Under Frequency, High Temp., Over Load, Fault AlarmLoad Segment Control Two programmable load segments, one continuous load segmentRemote Emergency Power Off (or)Remote Output Receptacle Control(Standard) Meets NFPA 70, NEC 645-11 (REPO connections located on the UPS rear panel)(Optional) UPS Load Segment Controlled Output Receptacles can be turned off and on using a remote isolated switch contact.Communications USB Port, RS-232C Serial Port, Optional SNMP/HTTP Agent Board (UPS Bundled UPSilon 2000 Software)MechanicalDimensions inches (mm)H x W x DSSGH-B Battery Module(2U) 3.5 x 19 x 21.3(88 x 482.6 x 540)(None - Batteries inside UPS)(2U) 3.5 x 19 x 21.3 (88 x 482.6 x 540)(2U) 3.5 x 19 x 21.3 (88 x 482.6 x 540)Weight lb. (kg)Ten-Year VRLA Batteries (Standard)SSGLi-4 Ten-Year Lithium-Ion Battery OptionSSGLi-8 2U Lithium-Ion Extended BankUPS With Internal VRLA batteries = 55 (24.5)With Internal Lithium batteries = 39.5 (17.9)External 2U Lithium Battery Bank = 39.15(2U) UPS Module = 32 (14.5)(2U) External Battery Module = 70.6 (32)N/AN/A(2U) UPS Module = 32 (14.5)(2U) External Battery Module = 70.6 (32)N/AN/AAgency Approvals -1 Models = UL 1778, CUL, FCC Class B, -2 Models = CE, UL 1778, CUL