122 469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDEMODBUS MEMORY MAP COMMUNICATIONS GUIDEF146Unsigned16 bit integer ANALOG IN DIFFERENTIAL LOGIC0 1>2 (or 3>4)1 2>1 (or 4>3)2 1<>2 (or 3<>4)F147Unsigned16 bit integerANALOG IN DIFFERENTIAL ACTIVEWHEN0 Always1f Start/RunF148Unsigned16 bit integer TORQUE DISPLAY UNITS0 Newton-meter1 Foot-poundF149Unsigned16 bit integer UNDERVOLTAGE TRIP MODE0 1-Phase1 3-PhaseF150Unsigned32 bit integer IP ADDRESSIP address, subnet mask or default gateway. Each bytein this register represents one octet of an IP address.For example: 0x015EDA1F represents address1.94.218.31F151Unsigned16 bit integer DEVICENET CONNECTION STATUS0 Nonexistent1 Configuring2 --3 Established4 Time Out5 Deferred DateF152Unsigned16 bit integer ETHERNET STATUSBIT 0 DiagnosticBIT 1 Connection StatusBIT 2 Not UsedBIT 3 Ethernet Link StatusF153Unsigned16 bit integer DEVICENET PORT STATUS0 Not Powered1 Port Operational2 Internal Configuration Error - DataSize Larger Than Confirmed3 Unrecoverable Fault4 Minor FaultF154Unsigned16 bit integer DEVICENET LINK STATUS0 Not Online, Not Powered1 Online, Connected2 --3 Online, Not Connected4 Critical Link Failure5 Connection TimeoutTable 8: Data Formats (Sheet 14 of 15)CODE TYPE DEFINITION