26 469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDEMODBUS MEMORY MAP COMMUNICATIONS GUIDE... ...020F ReservedSYSTEMSTATUS 0210 General status 0 65535 1 -- F140 00211 Output relay status 0 63 1 -- F141 00212 Reserved0213 Reserved... ...021F ReservedLAST TRIPDATA ALARM 0220 Cause of last trip 0 49 1 -- F134 00221 Time of last trip (2 words) -- -- -- -- F19 --0223 Date of last trip (2 words) -- -- -- -- F18 --0225 Motor speed during trip 0 1 1 -- F135 00226 Pre-trip tachometer RPM 0 3600 1 RPM F1 00227 Phase A pre-trip current 0 100000 1 A F9 00229 Phase B pre-trip current 0 100000 1 A F9 0022B Phase C pre-trip current 0 100000 1 A F9 0022D Pre-trip motor load 0 2000 1 FLA F3 0022E Pre-trip current unbalance 0 100 1 % F1 0022F Pre-trip ground current 0 5000 1 A F11 00231 Phase A pre-trip differential current 0 5000 1 A F1 00232 Phase B pre-trip differential current 0 5000 1 A F1 00233 Phase C pre-trip differential current 0 5000 1 A F1 00234 Hottest stator RTD during trip 0 12 1 -- F1 00235 Pre-trip temperature of hottest stator RTD –50 250 1 °C F4 00236 Hottest bearing RTD during trip 0 12 1 -- F1 00237 Pre-trip temperature of hottest bearing RTD –50 250 1 °C F4 00238 Hottest other RTD during trip 0 12 1 -- F1 00239 Pre-trip temperature of hottest other RTD –50 250 1 °C F4 0023A Hottest ambient RTD during trip 0 12 1 -- F1 0023B Pre-trip ambient RTD temperature –50 250 1 °C F4 0023C Pre-trip voltage Vab 0 20000 1 V F1 0023D Pre-trip voltage Vbc 0 20000 1 V F1 0023E Pre-trip voltage Vca 0 20000 1 V F1 0023F Pre-trip voltage Van 0 20000 1 V F1 00240 Pre-trip voltage Vbn 0 20000 1 V F1 00241 Pre-trip voltage Vcn 0 20000 1 V F1 00242 Pre-trip system frequency 0 12000 1 Hz F3 00243 Pre-trip real power –50000 50000 1 kW F12 00245 Pre-trip reactive power –50000 50000 1 kvar F12 00247 Pre-trip apparent power 0 50000 1 kVA F1 00248 Pre-trip power factor –99 100 1 -- F21 0Table 7: 469 MEMORY MAP (Sheet 8 of 90)GROUP ADDR(HEX) DESCRIPTION MIN. MAX. STEPVALUE UNITS FORMATCODE DEFAULT