COMMUNICATIONS GUIDE MODBUS MEMORY MAP469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE 711D4B Fault analog input 1 0 100 1 %range F1 01D4C Fault analog input 2 0 100 1 %range F1 01D4D Fault analog input 3 0 100 1 %range F1 01D4E Fault analog input 4 0 100 1 %range F1 01D4F Fault differential current 0 110 1 × CT F3 01D50 Reserved1D51 Reserved... ...1D7B Reserved1D7C Fault stator RTD temperature (in °F) –58 482 1 °F F4 1041D7D Fault bearing RTD temperature (in °F) –58 482 1 °F F4 1041D7E Fault other RTD temperature (in °F) –58 482 1 °F F4 1041D7F Fault ambient RTD temperature (in °F) –58 482 1 °F F4 104TESTOUTPUTRELAYS1D80 Force operation of relays 0 8 1 -- F139 01D81 Reserved1D82 Reserved... ...1D8F ReservedTESTANALOGOUTPUTS1D90 Force analog outputs 0 1 1 -- F126 01D91 Analog output 1 forced value 0 100 1 %range F1 01D92 Analog output 2 forced value 0 100 1 %range F1 01D93 Analog output 3 forced value 0 100 1 %range F1 01D94 Analog output 4 forced value 0 100 1 %range F1 01D95 Reserved1D96 Reserved... ...1DFE ReservedSPEED 2O/L SETUP 1DFF Speed 2 standard overload curve number 1 15 1 -- F1 41E00 Speed 2 time to trip at 1.01 x FLA 5 999999 1 s F10 1741451E02 Speed 2 time to trip at 1.05 x FLA 5 999999 1 s F10 341491E04 Speed 2 time to trip at 1.10 x FLA 5 999999 1 s F10 166671E06 Speed 2 time to trip at 1.20 x FLA 5 999999 1 s F10 79541E08 Speed 2 time to trip at 1.30 x FLA 5 999999 1 s F10 50721E0A Speed 2 time to trip at 1.40 x FLA 5 999999 1 s F10 36461E0C Speed 2 time to trip at 1.50 x FLA 5 999999 1 s F10 28001E0E Speed 2 time to trip at 1.75 x FLA 5 999999 1 s F10 16971E10 Speed 2 time to trip at 2.00 x FLA 5 999999 1 s F10 11661E12 Speed 2 time to trip at 2.25 x FLA 5 999999 1 s F10 8611E14 Speed 2 time to trip at 2.50 x FLA 5 999999 1 s F10 6661E16 Speed 2 time to trip at 2.75 x FLA 5 999999 1 s F10 533Table 7: 469 MEMORY MAP (Sheet 53 of 90)GROUP ADDR(HEX) DESCRIPTION MIN. MAX. STEPVALUE UNITS FORMATCODE DEFAULT