5-16 D60 Line Distance Relay GE Multilin5.2 PRODUCT SETUP 5 SETTINGS5The D60 supports the Manufacturing Message Specification (MMS) protocol as specified by IEC 61850. MMS is supportedover two protocol stacks: TCP/IP over ethernet and TP4/CLNP (OSI) over ethernet. The D60 operates as an IEC 61850server. The Remote Inputs/Outputs section in this chapter describe the peer-to-peer GSSE/GOOSE message scheme.The REMOTE I/O TRANSFER METHOD selects the method used to transfer remote input/output data. This can be either IEC61850 GSSE, IEC 61850 GOOSE, or none (remote inputs/outputs disabled). GOOSE messages are more efficient and canmake use of Ethernet priority tagging and virtual LAN functionality. All relays exchanging remote input/output data must beset to the same transfer method.The DEFAULT GSSE/GOOSE UPDATE TIME sets the time between GSSE or GOOSE messages when there are no remote out-put state changes to be sent. When remote output data changes, GSSE or GOOSE messages are sent immediately. Thissetting controls the steady-state ëheartbeatí time interval.The GOOSE TRANSMIT VLAN PRIORITY setting indicates the Ethernet priority of GOOSE messages. This allows GOOSEmessages to have higher priority than other Ethernet data. The GOOSE TRANSMIT ETYPE APPID setting allows the selectionof a specific application ID for each GOOSE sending device. This value can be left at its default if the feature is notrequired. Both the GOOSE TRANSMIT VLAN PRIORITY and GOOSE TRANSMIT ETYPE APPID settings are required by IEC 61850.The LOGICAL DEVICE NAME setting represents the MMS domain name (IEC 61850 logical device) where all IEC/MMS logicalnodes are located. The IEC/MMS TCP PORT NUMBER setting allows the user to change the TCP port number for MMS con-nections. The INCLUDE NON-IEC DATA setting determines whether or not the ìURî MMS domain will be available. This# SERVER# CONFIGURATIONLOGICAL DEVICE NAME:IECDeviceRange: up to 16 alphanumeric charactersMESSAGE IEC/MMS TCP PORT:NUMBER: 102Range: 1 to 65535 in steps of 1MESSAGE INCLUDE NON-IECDATA: EnabledRange: Disabled, Enabled# IEC 61850 LOGICAL# NODE NAME PREFIXES# PIOC LOGICAL NODE# NAME PREFIXESMESSAGE # PTOC LOGICAL NODE# NAME PREFIXES↓MESSAGE # PTRC LOGICAL NODE# NAME PREFIXES# MMXU DEADBANDS## MMXU1 DEADBANDS#MESSAGE # MMXU2 DEADBANDS#MESSAGE # MMXU3 DEADBANDS#MESSAGE # MMXU4 DEADBANDS## GGIO2 CONTROL# CONFIGURATION# GGIO2 CF SPCSO 1#MESSAGE # GGIO2 CF SPCSO 2#↓MESSAGE # GGIO2 CF SPCSO32#