5-178 D60 Line Distance Relay GE Multilin5.6 CONTROL ELEMENTS 5 SETTINGS55.6.9 MONITORING ELEMENTSa) MAIN MENUPATH: SETTINGS !" CONTROL ELEMENTS !" MONITORING ELEMENTSb) BREAKER ARCING CURRENTPATH: SETTINGS !" CONTROL ELEMENTS !" MONITORING ELEMENTS ! BREAKER 1(4) ARCING CURRENTThere is one Breaker Arcing Current element available per CT bank, with a minimum of 2 elements. This element calcu-lates an estimate of the per-phase wear on the breaker contacts by measuring and integrating the current squared passingthrough the breaker contacts as an arc. These per-phase values are added to accumulated totals for each phase and com-pared to a programmed threshold value. When the threshold is exceeded in any phase, the relay can set an output operandto ì1î. The accumulated value for each phase can be displayed as an actual value.# MONITORING# ELEMENTS# BREAKER 1# ARCING CURRENT See below.MESSAGE # BREAKER 2# ARCING CURRENT See below.MESSAGE # BREAKER# FLASHOVER 1 See page 5ñ180.MESSAGE # BREAKER# FLASHOVER 2 See page 5ñ180.MESSAGE # VT FUSE FAILURE 1# See page 5ñ184.MESSAGE # VT FUSE FAILURE 2# See page 5ñ184.MESSAGE # OPEN POLE# See page 5ñ185.# BREAKER 1# ARCING CURRENTBKR 1 ARC AMPFUNCTION: DisabledRange: Disabled, EnabledMESSAGE BKR 1 ARC AMPSOURCE: SRC 1Range: SRC 1, SRC 2, SRC 3, SRC 4MESSAGE BKR 1 ARC AMP INIT-A:OffRange: FlexLogicô operandMESSAGE BKR 1 ARC AMP INIT-B:OffRange: FlexLogicô operandMESSAGE BKR 1 ARC AMP INIT-C:OffRange: FlexLogicô operandMESSAGE BKR 1 ARC AMPDELAY: 0.000 sRange: 0.000 to 65.535 s in steps of 0.001MESSAGE BKR 1 ARC AMP LIMIT:1000 kA2-cycRange: 0 to 50000 kA 2-cycle in steps of 1MESSAGE BKR 1 ARC AMP BLOCK:OffRange: FlexLogicô operandMESSAGE BKR 1 ARC AMPTARGET: Self-resetRange: Self-reset, Latched, DisabledMESSAGE BKR 1 ARC AMPEVENTS: DisabledRange: Disabled, Enabled