5-82 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUALPRODUCT SETUP CHAPTER 5: SETTINGS5Figure 5-35: Commands panelFltRptRFLO1.RsStat.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR FAULT REPORTS. "sbo"here is select-before-operate. Enhanced security means that the F60 reports to the client the breaker 1 position at theend of the command sequence.LLN0.EvtRcdClr.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR EVENT RECORDS.LPHD1.RsStat.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR ALL RELAY RECORDS.OscRDRE1.RcdTrg.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command FORCE TRIGGER.OscRDRE1.MemClr.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR OSCILLOGRAPHY.DatLogRDRE1.MemClr.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-securityThis setting selects the control model clients must use to successfully control the command CLEAR DATA LOGGER.CBArc0SCBR1.MemClr.ctlModelRange: direct-with-normal-security, sbo-with-normal-securityDefault: direct-with-normal-security