5-260 F60 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 5: SETTINGS5Make the following changes to setting group control in the SETTINGS CONTROL ELEMENTS SETTING GROUPS menu:SETTING GROUPS FUNCTION: “Enabled”SETTING GROUPS BLK: “Off”GROUP 2 ACTIVATE ON: “SELECTOR 1 POS 2"GROUP 3 ACTIVATE ON: “SELECTOR 1 POS 3"GROUP 4 ACTIVATE ON: “SELECTOR 1 POS 4"GROUP 5 ACTIVATE ON: “Off”GROUP 6 ACTIVATE ON: “Off”Make the following changes to selector switch element in the SETTINGS CONTROL ELEMENTS SELECTOR SWITCH SELECTOR SWITCH 1 menu to assign control to user programmable pushbutton 1 and contact inputs 1 through 3:SELECTOR 1 FUNCTION: “Enabled”SELECTOR 1 FULL-RANGE: “4”SELECTOR 1 STEP-UP MODE: “Time-out”SELECTOR 1 TIME-OUT: “5.0 s”SELECTOR 1 STEP-UP: “PUSHBUTTON 1 ON”SELECTOR 1 ACK: “Off”SELECTOR 1 3BIT A0: “CONT IP 1 ON”SELECTOR 1 3BIT A1: “CONT IP 2 ON”SELECTOR 1 3BIT A2: “CONT IP 3 ON”SELECTOR 1 3BIT MODE: “Time-out”SELECTOR 1 3BIT ACK: “Off”SELECTOR 1 POWER-UP MODE: “Synchronize”Now, assign the contact output operation (assume the H6E module) to the selector switch element by making the followingchanges in the SETTINGS INPUTS/OUTPUTS CONTACT OUTPUTS menu:OUTPUT H1 OPERATE: “SELECTOR 1 BIT 0"OUTPUT H2 OPERATE: “SELECTOR 1 BIT 1"OUTPUT H3 OPERATE: “SELECTOR 1 BIT 2"Finally, assign configure user-programmable pushbutton 1 by making the following changes in the SETTINGS PRODUCTSETUP USER-PROGRAMMABLE PUSHBUTTONS USER PUSHBUTTON 1 menu:PUSHBUTTON 1 FUNCTION: “Self-reset”PUSHBUTTON 1 DROP-OUT TIME: “0.10 s”The figure shows the logic for the selector switch.