LX: OPM_LPA_11U_5K0_10K_1US_V021 11 GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)GE Digital Energyg4.4.1.2 Installation procedure:input voltage 120Vac (optional, 5-6kVA only), output voltage 120/208/220/230/240Vac.If a battery extension pack is to be installed, please proceed with section 4.4.5.If 2, 3 or 4 parallel operating units will be installed, please proceed with section 4.4.6.The numbers between (brackets) refer to figure 19 and 20 in section 5.1.1. Mount the levellers: position A to fix the UPS to the floor,position B to lift the castors from the floor. Please refer tofigure 6, step 1.2. Loosen the screws and remove the conduit boxes (17, 2x)and the cover plate (11).3. Make sure that all circuit breakers (7-8-9) are in ‘off’position (down). Please refer to fig. 6, step 3.4. Input/output connection:Lead the input/output cables through the cable inlet. If thecables come from below (recommended for 8kVA and10kVA models), you can rotate the cable inlet 90 degrees.Connect the input wires to the input terminals (11b).Connect the output wires to the output terminals (11a).Please refer to section 4.4.2.2 (input) and 4.4.3 (output)for detailed information.5. Re-install the cover plate (11) and the conduit boxes (17,2x).6. An emergency shutdown switch can be connected toconnector J3 on the RS232/Contact Interface Card,between pins 3 and 4. See section 6.2 for moreinformation.7. For advanced communication possibilities, theRS232/contact interface port (12a) can be connected to acomputer system. See section 6.1 for more information.8. The middle ‘option slot’ (13) allows easy installation ofplug-in cards: SNMP Card or Relay Card. See sections6.3 and 6.4 for more information.9. The right ‘option slot’ (14) allows easy installation of theRPA-card (Redundant Parallel Architecture). If the card isalready mounted, and if the unit is intended to be usedstand-alone, a bus terminator (delivered with the unit) hasto be placed in one of the two bus connectors on the card.If the unit will be part of a parallel system, see sections4.4.6 and 7.3 for more information.10. Connect the utility power to the UPS.11. If hardware modifications were necessary in step 4because the output voltage is different from the default(208Vac), software modifications should be performed aswell. Proceed with 4.4.4.12. For a quick start proceed with section 5.2 ‘Start-up’.Figure 7. LanPro® 5/6-11U:Installation procedure 120V input2L N456 78 91-2 BATTERYDISCONNECTED3-4 EMERGENCYSHUTDOWNsee 6.3-4see 4.4.6 / 7.3stand-alone,and RPA cardavailable: