LX: OPM_LPA_11U_5K0_10K_1US_V021 28 GE DE LanPro-11U UPS: Installation / User Manual 2.1 (US)GE Digital Energyg Service information on internal timer.Frequency tracking range: output converter frequency will follow the bypassfrequency within these limits before returning to its own internal frequency.Standard setting: nominal ±2%. Can be changed into nominal ±4% or ±6%. See5.3.4 Setup Menu.No-load shutdown: after a 10 minutes delay the UPS will shut down during utilityfailure if the load is < 2%. It will restart after the utility returns or when the unit isswitched off and on again.Default setting = 1 (active). For disabling this feature see 5.3.4.Start of the manual Quick Battery Test.See for more information section 5.4.2 'Quick Battery Test'Start of the manual Deep Battery Calibration Test.See for more information sections 5.4.3 'Deep Battery Calibration Test'Service information on internal UPS componentsService information on internal UPS componentsService information on internal UPS componentsBatt.Charger: 0 = off, 1 = float charging; 2 = top charge, 3 = boost charging,4 = maintenance chargeDuration of latest test performed, hh/mm/ssThe UPS transfers the load to bypass when the keys 'down' (2) and 'enter/reset' (3)on the front panel are depressed simultaneously for approx. 1 seconds. If thebypass supply is not within limits, the lower line will show the text 'UNAVAILABLE'.Service set up information whether the bypass is enabled (default) or disabled. Ifdisabled: UPS will NOT go to bypass. For disabling the bypass refer to the setupmenu (5.3.4).Service set up information about the total battery capacity. Information about theactual battery charge condition. For changing the programmed battery capacityrefer to the setup menu (5.3.4).Service set up information about frequency tracking speed for the inverter to followthe bypass frequency, LOW (1Hz/sec.) is the normal value and default. HIGH(5Hz/sec.) may be suitable if the UPS is connected to a generator with fastfrequency changes and the UPS must be synchronized to prevent alarms. Forchanging the lock speed refer to the setup menu (5.3.4).Service set-up information about the ECO-mode. By pressing ‘ENTER/RESET’the ECO-mode can be enabled or disabled, depending on the actual status. Inthis way the load will be supplied by way of the electronic bypass. If the ECO-mode is disabled the load will be supplied by the inverter. See also 4.5.5.Service set-up information about the autorestart function. This function can beswitched on or off by pressing ‘ENTER/RESET’, depending on the actual status.See also 4.5.6.767$034)5(45$1*(12/2$'48,&.%$77(5<7(6735(66(17(5&$/,%5$7(%$735(66'2:1(17(53)7+<5,6725%$777+<5,67259667+<5,67253)&219(57(5/$677(677,0(%$7&+$5*(5,19(57(5)25&(%<3$66SUHVV'2:1(17(5$8720$7,&%<3$66(1$%/('%$77(5<$K%$7&+$5*(3///2&.63(('1250$/(&2',6$%/('(17(55(6(7&+1*$8725(67$5721(17(55(6(7&+1*