3–16 350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUALSOFTWARE SETUP CHAPTER 3: INTERFACESThe 350 Site Device has now been configured via the Quick Connect feature for either USBor Ethernet communications. Proceed to Connecting to the Relay below, to begincommunications.3.2.3.3 Configuring Ethernet communicationsBefore starting, verify that the Ethernet cable is properly connected to the RJ-45 Ethernetport.NOTENOTE:350 supports a maximum of 3 TCP/IP sessions.1. Install and start the latest version of the EnerVista SR3 Setup Setup software (availablefrom the GE EnerVista CD). See the previous section for the installation procedure.2. Click on the Device Setup button to open the Device Setup window and click the AddSite button to define a new site.3. Enter the desired site name in the "Site Name" field. If desired, a short description ofthe site can also be entered. In this example, we will use “Substation 1” as the sitename.4. The new site will appear in the upper-left list.5. Click the Add Device button to define the new device.6. Enter the desired name in the "Device Name" field, and a description (optional).7. Select “Ethernet” from the Interface drop-down list. This will display a number ofinterface parameters that must be entered for proper Ethernet functionality.