CHAPTER 5: QUICK SETUP - FRONT CONTROL PANEL QUICK SETUP SETTINGS350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 5–35.1 Quick Setup settingsThis section provides an overview of the interfacing methods available with the 350 usingthe front control panel. For additional details on interface parameters (for example,settings, actual values, etc.), refer to the individual chapters.PATH: QUICK SETUP >PH CT PRIMARYRange: 1 A to 6000 A in steps of 1Default: 500 AGND CT PRIMARYRange: 1 A to 6000 A in steps of 1Default: 50 APH TOC FUNCTIONRange: Trip, Disabled, Latched Alarm, AlarmDefault: Trip↘PH TOC PICKUPRange: 0.04 to 20.00 x CTDefault: 1.00 x CTPH TOC CURVERange: ANSI Extremely/Very/Moderately/Normally Inverse, DefiniteTime, IEC Curve A/B/C and Short, IAC Extreme/Very/Inverse/Short, UserCurve, FlexCurve™ A/B (programmable curves)Default: Extremely InversePH TOC TDMRange: 0.50 to 20.00Default: 1.00GND TOC FUNCTIONRange: Disabled, Trip, Latched Alarm, AlarmDefault: Disabled↘GND TOC PICKUPRange: 0.04 to 20 x CTDefault: 1.00 x CTGND TOC CURVERange: ANSI Extremely/Very/Moderately/Normally Inverse; DefiniteTime; IEC Curve A/B/C /Short Inverse; IAC Extreme/Very/Inverse/ShortInverse; User Curve, FlexCurve™ A/B (programmable curves)Default: Extremely InverseGND TOC TDMRange: 0.50 to 20.00Default: 1.00SENS GND TOC FUNCTION [WHEN SPECIFICALLY ORDERED]Range: Disabled, Trip, Latched Alarm, AlarmDefault: Disabled↘