CHAPTER 4: ACTUAL VALUES A3 RECORDS350 FEEDER PROTECTION SYSTEM – INSTRUCTION MANUAL 4–94.4 A3 RecordsThe 350 has an event recorder which runs continuously. All event records are stored inmemory such that information is maintained for up to 3 days even after losing relaycontrol power. The events are displayed from newest to oldest event. Each event has aheader message containing a summary of the event that occurred, and is assigned anevent number equal to the number of events that have occured since the recorder wascleared. The event number is incremented for each new event.4.4.1 Event recordsThe Event Recorder runs continuously, capturing and storing the last 256 events. All eventsare stored in non-volatile memory, where the information is maintained, even in the casewhere relay control power is lost.PATH: ACTUAL VALUES > A3 RECORDS > EVENT RECORDSTable 1: Example of Event RecordA3 EVENT REC T:778E778 Jan 30,2009BKR Stat Open16:30:23.324▶ E778, CONTROLBKR Stat OpenPHASE A CURRENT0.0 A 0° Lag▼E778, CONTROLBKR Stat OpenPHASE B CURRENT0.0 A 0° Lag▼E778, CONTROLBKR Stat OpenPHASE C CURRENT0.0 A 0° Lag▼E778, CONTROLBKR Stat Open|GROUND CURRENT0.0 A 0° Lag▼E778, CONTROLBKR Stat OpenNTRL GND CURRENT0.0 A▼E778, CONTROLBKR Stat OpenTHERM CAP PH A0.0%▼E778, CONTROLBKR Stat OpenTHERM CAP PH B0.0%▼E778, CONTROLBKR Stat OpenTHERM CAP PH C0.0%