UR SERIES – COMMUNICATIONS GUIDE 4-1UR SeriesChapter 4: DNP communicationDNP communicationThis chapter outlines the Distributed Network Protocol (DNP).4.1 Device profile documentThe following table provides a ‘Device Profile Document’ in the standard format defined in the DNP 3.0 Subset DefinitionsDocument.Table 4-1: DNP v3.00 device profile(Also see the IMPLEMENTATION TABLE in the following section)Vendor Name: General Electric MultilinDevice Name: UR Series RelayHighest DNP level supportedFor Requests: Level 2For Responses: Level 2Device function Master SlaveNotable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the completelist is described in the attached table):Binary Inputs (Object 1)Binary Input Changes (Object 2)Binary Outputs (Object 10)Control Relay Output Block (Object 12)Binary Counters (Object 20)Frozen Counters (Object 21)Counter Change Event (Object 22)Frozen Counter Event (Object 23)Analog Inputs (Object 30)Analog Input Changes (Object 32)Analog Deadbands (Object 34)Time and Date (Object 50)File Transfer (Object 70)Internal Indications (Object 80)