GE Multilin L60 Line Phase Comparison System 1-91 GETTING STARTED 1.3 ENERVISTA UR SETUP SOFTWARE19. Enter the relay IP address specified in the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IPADDRESS) in the “IP Address” field.10. Enter the relay slave address and Modbus port address values from the respective settings in the SETTINGS Ö PROD-UCT SETUP ÖØ COMMUNICATIONS ÖØ MODBUS PROTOCOL menu.11. Click the Read Order Code button to connect to the L60 device and upload the order code. If an communications erroroccurs, ensure that the three EnerVista UR Setup values entered in the previous steps correspond to the relay settingvalues.12. Click OK when the relay order code has been received. The new device will be added to the Site List window (orOnline window) located in the top left corner of the main EnerVista UR Setup window.The Site Device has now been configured for Ethernet communications. Proceed to the Connecting to the L60 section tobegin communications.1.3.4 USING THE QUICK CONNECT FEATUREa) USING QUICK CONNECT VIA THE FRONT PANEL RS232 PORTBefore starting, verify that the serial cable is properly connected from the laptop computer to the front panel RS232 portwith a straight-through 9-pin to 9-pin RS232 cable.1. Verify that the latest version of the EnerVista UR Setup software is installed (available from the GE EnerVista CD oronline from http://www.GEmultilin.com). See the Software Installation section for installation details.2. Select the “UR” device from the EnerVista Launchpad to start EnerVista UR Setup.3. Click the Quick Connect button to open the Quick Connect dialog box.4. Select the Serial interface and the correct COM Port, then click Connect.5. The EnerVista UR Setup software will create a site named “Quick Connect” with a corresponding device also named“Quick Connect” and display them on the upper-left corner of the screen. Expand the sections to view data directlyfrom the L60 device.Each time the EnerVista UR Setup software is initialized, click the Quick Connect button to establish direct communica-tions to the L60. This ensures that configuration of the EnerVista UR Setup software matches the L60 model number.b) USING QUICK CONNECT VIA THE REAR ETHERNET PORTSTo use the Quick Connect feature to access the L60 from a laptop through Ethernet, first assign an IP address to the relayfrom the front panel keyboard.1. Press the MENU key until the SETTINGS menu is displayed.2. Navigate to the SETTINGS Ö PRODUCT SETUP ÖØ COMMUNICATIONS ÖØ NETWORK Ö IP ADDRESS setting.3. Enter an IP address of “1.1.1.1” and select the ENTER key to save the value.4. In the same menu, select the SUBNET IP MASK setting.5. Enter a subnet IP address of “255.0.0.0” and press the ENTER key to save the value.