5-214 B30 BUS DIFFERENTIAL SYSTEM – INSTRUCTION MANUALCONTROL ELEMENTS CHAPTER 5: SETTINGS5Figure 5-112: Selector switch logic5.8.5 Digital elementsSETTINGS CONTROL ELEMENTS DIGITAL ELEMENTS DIGITAL ELEMENT 1(48) DIGITAL ELEMENT 1 DIGITAL ELEMENT 1FUNCTION: DisabledRange: Disabled, Enabled DIG ELEM 1 NAME:Dig Element 1Range: up to 16 alphanumeric characters DIG ELEM 1 INPUT:OffRange: FlexLogic operand DIG ELEM 1 PICKUPDELAY: 0.000 sRange: 0.000 to 999999.999 s in steps of 0.001 DIG ELEM 1 RESETDELAY: 0.000 sRange: 0.000 to 999999.999 s in steps of 0.001 DIGITAL ELEMENT 1PICKUP LED: EnabledRange: Disabled, Enabled DIG ELEM 1 BLOCK:OffRange: FlexLogic operand DIGITAL ELEMENT 1TARGET: Self-resetRange: Self-reset, Latched, Disabled DIGITAL ELEMENT 1EVENTS: DisabledRange: Disabled, Enabled