Condition for the PCB data:1.Working ambient temperature:-10℃~70℃, relative humidity:30%~95%2.Preserved ambient temperature:-20℃~80℃,relative humidity:30%~95%3.Power supply:220VAC、50/60Hz,voltage range:160V~250V4.Precise of temperature control:±1℃0010451167 PCB information – port and definitionP1——connect to external power supply, live line: L (220VAC)P2——connect to external power supply, neutral line: N (0VAC)P3、4、5、6——control external load, neutral line: N1、N2、N3、N4(0VAC)P7——control external load, electrical heat: HEAT (control output 220VAC)P8——control external load, health function: OXYGEN (control output 220VAC)P9——control external load, humidification: HUMI (control output 220VAC)P10——control external load, SWING(control output 220VAC)P11——control external load, WATER PUMP(control output 220VAC)P12——control external load, indoor fan motor low speed: L(control output 220VAC)P13——control external load, indoor fan motor mid speed: M(control output 220VAC)P14——control external load, indoor fan motor high speed: H(control output 220VAC)P15——communication with fixed frequency single outdoor unit: COMM(0~220VAC)P16——input control, signal live line: L’(220VAC)P17——input control, signal neutral line: N’(0VAC)CN1——input port of transformer (220VAC)CN2——input port 1 of transformer (no use)CN3——input port 2 of transformer (no use)CN4——input port 3 of transformer (1-2、14VAC,3-4、12VAC)CN5——input control, connecting port to wired controller: CONTROLLER(three bits: 1. power supply:12VAC, 2. power supply: 0VAC, 3. communication: COMM.).CN6——input control, ambient temp.-coil temp. sensor connecting port: ROOM/PIPE(1-2、ROOM,3-4、PIPE。)Indoor ambient temp. sensor: R25=23KΩ+-2.5%,B25/50=4200K+-3%,range:(-40,80)Indoor coil temp. sensor: R25=10KΩ+-3%,B25/50=3700K+-3%,range:(-20,90)CN7——control external load, fresh air control: FRESH(1. blank, 2. power supply 0VDC, 3. controloutput: 12VDC.)CN8——input signal: FREEZE(no use)CN9——input control(no use)CN10——communication with fixed frequency single outdoor unit: (0~12VDC)CN11——input signal, door switch: DOOR(1-2 short circuit is normal, cut off P8 output)CN12——input signal, external alarm input: ALARM(1-3 short circuit is normal, if cut off, airconditioner stops work.)Note: For convertible type, cassette type, duct type units, CN11 and CN12 must be in shortcircuit, or PCB will display failure information.CN13——input signal, wiring port of remote receiver board: RECEIVE BOARD(1. power supply 5VDC,2. power supply 0VDC, 3. remote signal, 4. signal output of running lamp 0VDC, 5. signal output of timer