ControlInformation about the dosing pump 33© Lutz-Jesco GmbH 2015Subject to technical changes.150225BA-10221-02-V03Stepper Motor-driven Diaphragm Dosing Pump MAGDOS LK Operating Instructions5. Press Back.4 The Safety code is activated. You must enter it when accessingthe System setup menu.10.6.7.1 Entering the safety codeSafety code1 1 1 1OK8.2Next- +Fig. 40: Entering the safety code1. Use the + and - keys to set a value of 0 to 9 for the first digit of thecode and then press Next.2. Proceed as described under point 1 for the other digits.3. After entering all the digits, press OK.4 If your input is correct, the dosing pump displays the Systemsetup menu.i If you have forgotten the code, please contact Lutz-JescoGmbH.10.6.7.2 Deactivating the safety code1. Press Menu.2. Use the or key to choose the System setup menu item andpress OK.3. Enter the correct Safety code and press OK.4. Use the or key to choose the Safety code menu item andpress Setup.5. Keep pressing Next until On is selected.6. Press -.7. Press Back.ü The safety code is deactivated.10.6.8 Set „Factory setup“ menu itemResets the dosing pump‘s control unit settings to the factory defaultsetting.1. Use the or key to choose the Factory setup menu item andpress Setup.2. Press OK.4 The dosing pump displays the Language menu (menu 6.3); seealso “Menu settings at initial commissioning” on page 29.ü The dosing pump is reset to the factory setup setting.10.6.9 Set „Eco-Mode“ menu itemSetting energy-saving mode. Doing this changes the power consumption,the delivery capacity and the delivery pressure; see also “Technical Data”on page 12.1. Use the or key to choose the Eco-Mode menu item and pressSetup.You can choose from the following options:n Off (factory default setting),n Eco-Mode 1.2. Use the or key to choose the desired function and press OK.4 The system displays the selected Eco-Mode on the start screenafter the respective operating mode.Fig. 41: "Slow Motion 1" mode display in manual mode10.7 Information about the dosing pumpIn the Info menu item, you can find a wide range of information aboutyour dosing pump.1. Press Menu.2. Use the or key to choose the Info menu item and press OK.4 The dosing pump displays menu 7.1 Info 1.Info 1Strokes / min 180Capacity 3.80 l/StdCalibration 3.80 l/StdMenu7.1NextFig. 42: Display of menu Info 13. Keep pressing Next to get to subsequent Info menus.The Info menus display the following information:Menu InformationInfo 1 n Maximum strokes/minuten Maximum delivery capacity in l/hrn Calibrated delivery capacity in l/hrInfo 2 n Stroke volume at factory setting in mln Stroke volume after calibration in mlInfo 3 n Running time of the dosing pump in hrs.n Total strokes of the dosing pump carried outInfo 4 n Software version and date of updatingn Part numbern Serial numberInfo 5 n Power supply voltagen Power frequencyInfo 6 Assignment of connection socket 1Info 7 Assignment of connection sockets 2 and 3Tab. 34: Explanation of the Info menus4. Press Menu to exit the Info menu.Manual mode Eco 1Menu Stop- +Literh0%0.00