GB - 12Parameter Description3.3 Factory setting for operating mode „GENERAL“Parameter Setting range Reso-lution Default Unit E basedonCP.00 password input 0…9999 1 - - - ud.01CP.01 actual frequency display -400…400 0,0125 0 Hz - ru.03CP.02 set frequency display -400…400 0,0125 0 Hz - ru.01CP.03 inverter state 0…255 1 0 - - ru.00CP.04 apparent current 0…6553,5 0,1 0 A - ru.15CP.05 Apparent current / peak value 0…6553,5 0,1 0 A - ru.16CP.06 utilization 0…65535 1 0 % - ru.13CP.07 actual DC voltage 0…1500B/C: 0…1000 1 0 V - ru.18CP.08 peak DC voltage 0…1500B/C: 0…1000 1 0 V - ru.19CP.09 output voltage 0…1167B/C: 0…778 1 0 V - ru.20CP.10 min. frequence 0…400 0,0125 0 Hz - oP.06CP.11 max. frequence forward 0…400 0,0125 70 Hz - oP.10CP.12 acc. time forward 0,00…300,00 0,01 5 s - oP.28CP.13 dec. time forward (-0.01 = CP.12) -0,01…300,00 0,01 5 s - oP.30CP.14 S-curve time 0,00…5,00 0,01 0,00(off) s - oP.32CP.15 boost 0,0…25,5 0,1 LTK % - uF.01CP.16 rated frequency 0…400 0,0125 50 Hz - uF.00CP.17 voltage stabilisation 1…1120B/C: 1…650(off) 1 0 V E uf.09CP.18 switching frequency 2/4/8/12/16 1 LTK kHz E uF.11CP.19 step value 1 -400…400 0,0125 5 Hz - oP.21CP.20 step value 2 -400…400 0,0125 50 Hz - oP.22CP.21 step value 3 -400…400 0,0125 70 Hz - oP.23CP.22 DC braking mode 0…506B/C: 0…9 1 7 - E Pn.28CP.23 DC braking time 0,00…100,00 0,01 10 s - pn.30CP.24 Max. ramp current 0…200 1 140 % - Pn.24CP.25 Max. constant current 0…200 1 200:off % - Pn.20CP.26 speed search condition 0…31B/C: 0…15 1 8 - E Pn.26CP.27 quick stop dec time 0,00…300,00 0,01 2 s - Pn.60CP.28 Response of ext. overtempera-ture.0…9B/C: 0…7 1 7 - - Pn.12CP.29 ANOUT1 function 0…29B/C: 0…26 1 2 - E An.31CP.30 ANOUT1 gain -20,00…20,00 0,01 1 - - An.33CP.31 relay output 1 / function 0…100B/C: 0…84 1 4 - E do.02further on next side