GB - 78Parameter Description6.2 Quick guide for operating mode „MULTI“Parameter Setting range Reso-lution Unit E Customer set-tingCP.00 password input 0...9999 1 – –CP.01 encoder 1 speed ±4000 0,125 rpm –CP.02 set value display ±4000 0,125 rpm –CP.03 inverter state 0...255 1 – –CP.04 apparent current 0...6553,5 0,1 A –CP.05 peak apparent current 0...6553,5 0,1 A –CP.06 actual torque ±32000,00 0,01 Nm –CP.07 actual DC voltage 0...1500 1 V –CP.08 peak DC voltage 0...1500 1 V –CP.09 output voltage 0...1167 1 V –CP.10 speed control configuration 0(off)...127 1 – –CP.11 DASM rated speed 0...64000 1 rpm –CP.12 DASM rated frequency 0,0...1600,0 0,1 Hz –CP.13 DASM rated current 0,0...1500,0 0,1 A –CP.14 DASM rated voltage 120...830 1 V –CP.15 DASM cos (phi) 0,50...1,00 0,01 – –CP.16 DASM rated power 0,10...1000,00 0,01 kW –CP.17 load mot. dependent para. 0...3 1 – ECP.18 boost 0,0...25,5 0,1 % –CP.19 rated frequency 0...400 0,0125 Hz –CP.20 encoder 1 (inc/r) 1…65535 1 Inc ECP.21 encoder 1 rotation 0...19 1 – ECP.22 Maximum speed 0...4000 0,125 rpm –CP.23 step value 1 ±4000 0,125 rpm –CP.24 step value 2 ±4000 0,125 rpm –CP.25 acc. time forward 0,00...300,00 0,01 s –CP.26 deceleration time (-0.01=CP.25) -0,01...300,00 0,01 s –CP.27 S-curve time 0.00(off)...5.00 0,01 s –CP.28 Torque reference source 0...6 1 – ECP.29 absolute torque reference ±32000,00 0,01 Nm –CP.30 KP speed 0...32767 1 – –CP.31 KI speed 0...32767 1 – –CP.32 switching frequency 2/4/8/12/16 (LTK) 1 kHz ECP.33 relay output 1 / function 0...100 1 – ECP.34 relay output 2 / function 0...100 1 – ECP.35 Limit switch / stopping mode 0...6 1 – –CP.36 External Fault / stopping mode 0...6 1 – –LTK = dep. on power circuit (see chapter 3.3); E=ENTER parameter