4: Advanced OperationsSecureLinx SLP Remote Power Manager 52Any Trap Status generates a Status trap and triggers the trap timer. A new trap isgenerated at the end of every timer period until the Status returns to a non-errorstatus.Table 4-5. Unit Status TrapsStatus Error DescriptionNormal Unit is working correctlyNoComm x Communication to the unit has been lostStatus Error DescriptionTable 4-6. Infeed Status TrapsStatus Error DescriptionOn Infeed is onOffError x Infeed should be on but no current is sensed at theinfeedNoComm x Communication to the infeed has been lostTable 4-7. Outlet Status TrapsStatus Error DescriptionOn Outlet is onOff Outlet is offOnWait Outlet Status in transitionOffWait Outlet Status in transitionOnError x Outlet should be off but current is sensed at theoutletOffError x Outlet should be on but no current is sensed at theoutletNoComm x Communication to the outlet has been lostNote: Traps are generated according to a hierarchical architecture; i.e. if a UnitStatus enters a trap condition, only the Unit Status trap is generated. Infeed andOutlet Status traps are suppressed until the Unit Status returns to Normal.Change trapThe Change trap is generated for all outlet status changes between any on/offconditions. Change traps include the outlet status, Location of the unit, and identifierand name of the affected outlet. For descriptions of the outlet status types, pleaserefer to the prior table.Load TrapThe Load trap is generated whenever the total input load on an infeed exceeds apreset threshold. Load traps include the reported input load, load status, Location ofthe unit, and identifier and name of the affected infeed.Any error state generates a Load trap and triggers the trap timer. A new trap isgenerated at the end of every timer period until the Load returns to a non-errorstatus.