©2006 Magnum Energy Inc.AC IN(Hardwire versions)AC OUT(Hardwire versions)Strainrelief’sACGround(In & Out)NeutralInHotOutNeutralOutHotInFigure 11, AC Wiring ConnectionsAC Input WiringYour inverter has an AC transfer feature that passes the AC inputpower to the inverter’s output. Connection to the AC input is made byhardwiring from a distribution panel as described below:1. Run an appropriately sized 2-conductor plus ground cable (fromthe AC distribution panel) through a strain-relief on the AC INopening. Refer to Table 4 for minimum wire size and overcurrentprotection required for the AC input wiring.2. Remove about two inches of the insulating jacket from the ACcable and separate the three wires and strip about 3/4” of insulationfrom each wire.3. Using an approved AC wire connectors, connect the incoming HotIn, Neutral In and Ground wires to the MM Series AC wires coloredblack (HOT IN), white (NEU IN) and green (AC GROUND) respectively.4. After making the AC input connections, secure the AC input cableby tightening the strain relief.The AC input wiring in the inverter is complete, review all AC wiringto ensure all connections are correct and secure.192.0 Installationhttp://www.wholesalesolar.com/inverters.htmlhttp://www.wholesalesolar.com/inverters.html