Part Number 000007651 05/10 5Section 2Installation InstructionsLocation of Ice MachineThe location selected for the ice machine must meet thefollowing criteria. If any of these criteria are not met,select another location.• The location must be free of airborne and othercontaminants.• The ice machine will operate in an air temperaturerange of 45°F to 110°F (7°C to 43°C) although therecommended air temperature is 60°F to 100°F(16°C to 38°C)• The ice machine will operate with water temperaturerange of 45°F to 90°F (7°C to 32°C) although therecommended water temperature range is 55°F to80° F (13°C to 27°C).• The location must not be near heat-generatingequipment or in direct sunlight.• The location must be capable of supporting theweight of the ice machine and a full bin of ice.• The location must allow enough clearance for water,drain and electrical connections in the rear of the icemachine.• The location must not obstruct airflow through oraround the ice machine. QF0406A airflow is in andout of the front of the ice machine. Refer to below forclearance requirements.Ice Machine Head Section ClearanceRequirementsIce Machine Heat of RejectionIce machines, like other refrigeration equipment, rejectheat through the condenser. It is helpful to know theamount of heat rejected by the ice machine when sizingthe air conditioning equipment where self-contained air-cooled ice machines are installed.ImportantFailure to follow these installation guidelines mayaffect warranty coverage.QF0406A Self-ContainedAir-CooledSelf-ContainedWater-CooledTop/Sides 5" (12.7 mm) NABack 5" (12.7 mm) NA! CautionThe ice machine must be protected if it will besubjected to temperatures below 32°F (0°C).Failure caused by exposure to freezingtemperatures is not covered by the warranty. See“Removal from Service/Winterization”.SeriesCondensing Unit Heat of Rejection*QF0406A 4000*B.T.U. / Hour