–16–Factory Equipment Refrigerant AmountsICE MACHINE HEAD SECTIONQ0600C/Q0800C/Q1000C/SU1000C/Q1400CEach ice machine head section ships from the factorywith an R-404A refrigerant charge appropriate for theentire system operation. The serial tag on the icemachine indicates the refrigerant charge. Therefrigerant charge is sufficient to operate the icemachine in ambient temperatures between -20°F(-28.9°C) and 130°F (54.4°C), (CVD1476, 50°F to110°F, 10°C to 43°C) with line set lengths of up to100 ft. (30.5 m).QDUAL Each QDUAL ice machine head section ships from thefactory with an R-404A refrigerant charge appropriatefor installations with up to 50" of refrigerant tubing. Theserial tag on the ice machine indicates the refrigerantcharge. For line set runs longer than 50 ft., 1 lb. ofadditional refrigerant must be added for each 10 ft. ofline set run. The receiver is designed to hold a chargesufficient to operate the ice machine in ambienttemperatures between -20°F (-28.9°C) and 120°F(49°C), with line set lengths of up to 100 feet (15 m)! CautionNever add more than nameplate charge to therefrigeration system for any application.! CautionThe 60-month compressor warranty (including the36-month labor replacement warranty) will not applyif the Manitowoc Ice Machine and Manitowoc CVD®Condensing Unit are not installed according tospecifications. This warranty also will not apply if therefrigeration system is modified with a condenser,heat reclaim device, or other parts or assemblies notmanufactured by Manitowoc Ice, Inc.