NTI ENTERPRISE ENVIRONMENT MONITORING SYSTEM23From the Non-Critical or Critical Alert Settings menu, the user can enable/disable alert messages to be sent when the sensor is inan alert state and configure when and how alert messages are sent. Additionally, from the Critical Alert Settings menu, the usercan configure the ENVIROMUX to capture a snapshot from an IP camera and attach the image to the alert message sent viaemail.Figure 19- Text Menu-Non-Critical and Critical Alert SettingsAlert SettingsDisable alerts Change to “Yes” to prevent alerts from being sent when this sensor’s status changesAlert Delay The alert delay is an amount of time the sensor must be in an alert condition before an alert issent. This provides some protection against false alarms. The Alert Delay value can be setfor 0-999 seconds or minutes.Notify Again Time Enter the amount of time in seconds, minutes, or hours (1-999) before an alert message will berepeatedNotify on Return to Normal The user can also be notified when the sensor readings have returned to the normal range bychanging to “Yes” for "Notify on return to normal" for a sensor.Auto Acknowledge Change to “Yes” to have alert notifications in the summary page return to normal stateautomatically when sensor readings return to normal.Enable Email Alerts Change to “Yes” to have alert notifications sent via EmailEnable Syslog Alerts Change to “Yes” to have alert notifications sent via Syslog messagesEnable SNMP traps Change to “Yes” to have alert notifications sent via SNMP traps (v2c)Enable SMS Alerts Change to “Yes” to have alert notifications sent via SMS (requires GSM modem)Email Subject Enter the subject to be viewed when an email alert message is receivedAttach IP camera capture Change to “Yes” to enable a snapshot to be taken from an IP camera and attached to the alertmessage (for critical alert messages only.)Selected IP camera Select which IP camera to take a snapshot from to be attached to an alert message (for criticalalert messages only)Associated output relay Choose which output relay to change state when sensor is in alertOutput relay on alert Choose the state the output relay should be in when the sensor is in alertOutput relay on return Choose the state the output relay should be in when the sensor returns to normalPress <Tab> to highlight Save and press <Enter> to save before pressing <Esc> to exit.