115ADVANCED PARAMETER-SETTING MODECommissioning manual Powerdrive MD2/FX4617 en - 2017.09 / e5.12.2 - Explanation of parameters in menu 1111.01 to 11.20 : Assignment of parametersApl.01 to Apl.20Adjustment range : 00.00 to 21.51Format: 16 bitsFactory setting : See table below.These parameters can be used, in order, to assign parametersApl.01 to Apl.20 of the «Quick setup» menu.Quick setupmenu Quick setupassignmentFactorysettingIf 11.43 = 1(Centrifugalapplication)Factorysetting If11.43 = 2(Brake motorapplication)11.01 Apl.01 09.21 12.4111.02 Apl.02 09.23 12.4211.03 Apl.03 09.24 12.4311.04 Apl.04 09.25 12.4411.05 Apl.05 12.74 12.4511.06 Apl.06 12.77 12.4611.07 Apl.07 12.78 12.4711.08 Apl.08 12.84 03.0511.09 Apl.09 12.87 00.0011.10 Apl.10 12.88 00.0011.11 Apl.11 14.03 00.0011.12 Apl.12 14.04 00.0011.13 Apl.13 14.08 00.0011.14 Apl.14 14.16. 00.0011.15 Apl.15 14.10 00.0011.16 Apl.16 14.11 00.0011.17 Apl.17 14.61 00.0011.18 Apl.18 14.60 00.0011.19 Apl.19 00.00 00.0011.20 Apl.20 00.00 00.00Note:If 11.43 is set to «Disabled» (0) or «Other application» (3), thedefault value of parameters 11.01 to 11.20 and Apl.01 toApl.20 will be 0.11.21 and 11.22 : Not used11.23 : Serial addressAdjustment range : 0 to 247Factory setting : 1Format: 16 bitsUsed to define the drive address in the case of control orsupervision via the serial link in MODBUS RTU. Avoid valuescontaining a zero as they are used to address groups of drives.Note:This parameter is used only for the MODBUS RTU link of thedrive’s P2 connector. To configure the MODBUS RTU link ofthe MDX-MODBUS option, refer to the manual ref. 4580 of theMDX-MODBUS option.11.24 : Serial modeAdjustment range : LS NET (0), MODBUS RTU (1)Format: 8 bitsThis parameter indicates which protocol is being used for thecurrent communication on the drive’s P2 connector serial link.LS NET (0):LS Net protocol.MODBUS RTU (1):MODBUS RTU protocol.11.25 : Baud rateAdjustment range : 1200 (0) to 115200 (9)Factory setting : 19200 (6)Format: 8 bitsUsed to select the data transfer speed for MODBUS RTU.Speed (baud) 11.251200 01200 11200 22400 34800 49600 519200 638400 757600 8115200 9Note:This parameter is used only for the MODBUS RTU link of thedrive’s P2 connector. To configure the MODBUS RTU link ofthe MDX-MODBUS option, refer to the manual ref. 4580 of theMDX-MODBUS option.11.26 : Min comms transmit delayAdjustment range : 0 to 100 msFactory setting : 2 msFormat: 16 bitsAs the serial link is 2-wire type, Rx is connected to Tx and Rx\to Tx\. A communication-related trip may occur if the receiverresponds to a request before the transmitter has had time toswitch. Parameter 11.26 is used to introduce a time betweenreception and return of data. After transmission of a request,the drive needs 1.5 ms before receiving the next command.The adjustment is made in 2 ms intervals.Note:This parameter is used only for the MODBUS RTU link of thedrive’s P2 connector. To configure the MODBUS RTU link ofthe MDX-MODBUS option, refer to the manual ref. 4580 of theMDX-MODBUS option.