140ADVANCED PARAMETER-SETTING MODECommissioning manual Powerdrive MD2/FX4617 en - 2017.09 / e5.17.2 - Explanation of parameters in menu 1616.01 : Timer 1 outputAdjustment range : Disabled (0) or Enabled (1)Format: 8 bitsThis parameter indicates the state of the output of timer 1.16.02 : Timer 1 sourceAdjustment range : 00.00 to 21.51Factory setting : 00.00Format: 16 bitsThis parameter is used to select the input source for timer relay1.Only «bit» type parameters can be assigned to these inputs. Ifan unsuitable parameter is addressed, the input will be frozenat 0.16.03 : Timer 1 mode selectAdjustment range : ON timer (0) or OFF timer (1)Factory setting : ON timer (0)Format: 8 bitsON timer (0):The relay is used for on-delay timing. The output changing toEnabled (1) is delayed in relation to the input changing to 1.OFF timer (1):The relay is used for off-delay timing. The output changing toDisabled (0) is delayed in relation to the input changing to 0.Note:Powering-up of the drive is not taken into account as a transitionof the input; the timer is therefore not activated.16.04 : Timer 1 unitAdjustment range : Second (0), Minute (1), Hour (2)Factory setting : Second (0)Format: 8 bitsSecond (0):The unit of time for the timer relay is the second.Minute (1):The unit of time for the timer relay is the minute.Hour (2):The unit of time for the timer relay is the hour.16.05 : Timer 1 valueAdjustment range : 0.0 to 60.0Factory setting : 0.0Format: 16 bitsThis parameter is used to set the delay period for timer 1. Theunit depends on the setting of 16.04.16.06 to 16.08 : Not used16.09 : Timer 1 output destinationAdjustment range : 00.00 to 21.51Factory setting : 00.00Format: 16 bitsThis parameter is used to select the destination of the outputfor timer 1.Only «bit» type parameters can be assigned to these outputs.If an unsuitable parameter is addressed, the output will befrozen at 0.16.10 : Not used16.11 : Timer 2 outputAdjustment range :Disabled (0) or Enabled (1)Format: 8 bitsThis parameter indicates the state of the output of timer 2.16.12 : Timer 2 sourceAdjustment range : 00.00 to 21.51Factory setting : 00.00Format: 16 bitsThis parameter is used to select the input source for timer relay2.Only «bit» type parameters can be assigned to these inputs. Ifan unsuitable parameter is addressed, the input will be frozenat 0.16.13 : Timer 2 mode selectAdjustment range : ON timer (0) or OFF timer (1)Factory setting : ON timer (0)Format: 8 bitsON timer (0):The relay is used for on-delay timing. The output changing toEnabled (1) is delayed in relation to the input changing to 1.OFF timer (1):The relay is used for off-delay timing. The output changing toDisabled (0) is delayed in relation to the input changing to 0.Note:Powering-up of the drive is not taken into account as a transitionof the input; the timer is therefore not activated.16.14 : Timer 2 unitAdjustment range : Second (0), Minute (1), Hour (2)Factory setting : Second (0)Format: 8 bitsSecond (0):The unit of time for the timer relay is the second.Minute (1):The unit of time for the timer relay is the minute.Hour (2):The unit of time for the timer relay is the hour.