Instruction ManualOCM Pro CF®OCM Pro CF - Rev. 07 as of 04.12.2012 Page 105Fig. 8-74 Pulse parameter settingSelect from the options below:- on_time s (select an impulse duration between 0.01 and 2.0 seconds. Theratio between impulse and break is 1:1. It is useful to increase the impulseduration beyond the 0.5 sec. default setting if slow PLC inputs or mechaniccounters are in use.)- amount m³ (defines the impulse weighting. The measured amount is goingto be integrated internally until the selected value has been equalled. An im-pulse signal with the previously programmed duration will be emitted after-wards and the integrated internal value is going to be set to 0 again. Thisprocedure will restart subsequently.)8.4.8 Parameter Menu „Control unit“Fig. 8-75 Control unit basic settingsThis menu allows you to adjust the transmitter to almost any waste water appli-cation for optimum performance. It enables to execute slide valve and torquemonitoring as well as quick close control or automatic flush functions.You can find more comprehensive information on setup and functional principlein Chapter 6.5.The flow controller function is only possible to be used in conjunction withtransmitters type >M4<. type >S4< allows the according parameters to be setas well, the transmitter however nor is equipped with outputs for regulatoroperation neither with respective connections.Function The additional submenus are not indicated before the function has been ena-bled by pressing the >ALT< key. No regulator setting options will be shown ifthe regulator has not been enabled.Fig. 8-76 Enabling the control unit