Installing racks66ANSI Hardware Installation Manual3HH-12893-AAAA-TCZZA Issue: 09DRAFT4.3.1 Parts listGeneral installation components include the following:• 7360 ISAM FX supported rack• 7360 ISAM WM supported rack• adapter plate assembly kit; one required per rack (not included with rack; orderseparately)• concrete anchor setting tool; one required per installation site (not included withrack; order separately)Seismic installation components include the following:• seismic rack extender; one optional per rack (not included with rack; orderseparately). Order the height of seismic rack extender required to convert the 7-ftrack to the height of the CO where the product is being installed. This componentextends the 7-ft rack, connecting to the CO overhead cable raceway rails only—it does not allow additional shelf installation.• seismic anchor bolt, size M12/25 (12 mm diameter bolt with 25 mm grip), fourrequired per rack (not included with rack; order separately)• seismic anchor bolt, size M12/50 (12 mm diameter bolt with 50 mm grip), fourrequired per rack (not included with rack; order separately)Non-seismic installation components include the following:• floor mounting hardware kit; one kit required per rack (not included with rack;order separately)• anchor bolt, size M12/25 (12 mm diameter bolt with 25 mm grip), two or fourrequired per rack dependent on installation practice (not included with rack; orderseparately)4.3.2 Recommended toolsThe following tools are recommended:• extension cord, 50 ft (15 m)• flathead and #2 Phillips screwdrivers• handling materials, tools, method, and packing material for hazardous wastematerial removal, if required• level, 3 ft (1 m)• rotary impact drill and associated drill bits• safety glassesNote — The standard anchor is M12/25. In applications wherethe floor is not level and requires shimming greater than 0.125in. (3.175 mm), the longer anchor (M12/50) may be required. Inall cases, make sure that the minimum embedment mark on theanchor is at or below the level of the concrete.