TERMOROSSELLA PLUS DSA / FORNO DSA – TERMONICOLETTA DSA / FORNO DSA7197100 - IT - EN - DE - FR 176. SAFETY DEVICES envisioned by Regulations in vigour.7. CIRCULATION PUMP : . It would be better to install it on the return in order to avoid that it could disconnect itself at very high watertemperatures but checking that it does not drive water in the open expansion tank otherwise it should cause a continuous wateroxygenation with consequent, fast corrosion of boiler body. It must be not to avoid a forced circulation in the open expansion tank.Furthermore it must be electrically connected to a thermostat or a electronic control unit that can be purchased with the thermo-product as OPTIONAL part.8. AUTOMATIC THERMOSTATIC MIXING VALVE – (see chapter 2.3)IMPORTANT: temperature safety sensors must be in place on the machine or at a distance no greater than 30 cm from the flow connectionof the thermo-product. Whenever the thermo products lack a device, those missing can be installed on the thermo product flow pipe,within a distance no greater than 1m from the thermo product.ATTENTION: For no reason must the fire be ignited before the system has been completely filled with water; doing this wouldlead to serious damage of the entire structure. The system must be filled by means of the loading pipe directly from the open tankin a way to prevent an excessive pressure of the water network deforming the body of the thermo heating stove.The system must be kept constantly full of water even during the periods when the use of the thermo-heating stove is not requested. Duringthe winter, inactivity must be faced with the addition of antifreeze.2.2. CLOSED expansion Tank systemIt is COMPULSORY that the CLOSED expansion Tank system is provided with:1. A 3 bar SAFETY VALVE: maximum operation pressure allowed for the system is 3 bar (equal to 30 m of the water column). Higherpressures can cause deformation and breakage of the boiler body2. AUTOMATIC THERMOSTATIC MIXING VALVE – (see chapter 2.3)3. HEAT DISCHARGE VALVE or HEAT SAFETY DISCHARGE (positive safety, therefore, this continues discharge, should the valvebe damaged)4. CLOSED EXPANSION Tank5. PUMP CONTROL THERMOSTAT6. NOISE ALARM ACTIVATION THERMOSTAT7. NOISE ALARM8. TEMPERATURE INDICATOR9. PRESSURE INDICATOR10. PUMP SYSTEMIMPORTANT: temperature safety sensors must be in place on the machine at a distance no greater than 30 cm from the flow connectionof the thermo-product. Whenever the thermo products lack a device, those missing can be installed on the thermo product flow pipe,within a distance no greater than 1m from the thermo product.IT IS MA NDATORY that the thermo products for domestic heating inserted in CLOSED Tank heating systems, must be internally equipped,with a cooling circuit, prepared by the unit manufacturer, which is activated by a thermal safety valve (see chapter 2.4) which does notrequire auxiliary power and can guarantee that the standard set temperature limit is not exceeded. Connection between the power supplyunit and the valve must be free from interceptions. Cooling circuit upstream pressure must be at least 1,5 bar.2.3. AUTOMATIC THERMOSTATIC MIXER VALVE - (OPTIONAL)The automatic thermostatic mixer valve finds applications in solid fuel heat generators as it prevents cold water return in the exchanger.Routes 1 and 3 are always open and, along with the pump installed on the return (R Picture 6 at page 56), they guarantee water circulationinside the biomass boiler exchanger (CB). An elevated return temperature, allows efficiency improvement, reduces formation of smokecondensation and prolongs the boiler life span.Valves on the market have different calibrations. NORDICA advises use of model 55°c with 1” hydraulic connections. Once the valvecalibration temperature is reached, route 2 opens and the boiler water goes to the system via the flow (M).IMPORTANT lack of installation of the device voids the heat exchanger warranty.2.4. HEAT DISCHARGE VALVE - (OPTIONAL)Solid fuel thermo products must be installed with safety devices determined by laws in vigour.For this reason the thermo products is equipped with a heat discharge coil.The heat discharge coil must have one side connected to the water network (A chapter 14) and the other rot drainage network (C). Whenthe safety temperature is reached, the heat discharge valve, the bulb of which is to be connected to attachment B, enables the intake ofcold water in the boiler coil, discharging the excess heat out of pipe C towards a conveniently installed drain.Cooling circuit upstream pressure must be at least 1,5 bar.2.5. SYSTEM CONNECTION AND FILLINGSome examples, purely indicative of the installation, are reported at chapter 12, while the connections to the thermoproduct are reportedat chapter 14.ATTENTION: The filling of the system must take place exclusively by the natural fall of the water from the open expansion tankthrough the feed pipe in order to avoid that a too high water system grid pressure could change or cause the explosion of