How to Use FlashScan Poll 3URJUDP &KDQJHAFC-600 Programming PN 51032:A 3/8/99 37+RZWR8VH)ODVK6FDQ3ROO)ODVK6FDQ3ROO2SWLRQVFrom the Program Change Selection screen (Figure 7 on page 14), press the 4 key toaccess the FlashScan Poll selection screen (Figure 44).)LJXUH )ODVK6FDQ 3ROO 6HOHFWLRQ 6FUHHQThis menu allows the selection of CLIP (Classic Loop Interface Protocol) or FlashScandetectors and modules for each loop. Once this screen is accessed, the cursor will bepositioned underneath the Loop #1 Detector selection, blinking the currently selectedprotocol type. The default selections are shown in Figure 44. This indicates that bothLoop #1 and Loop #2 detectors and modules are selected to use CLIP devices. IfFlashScan devices are to be employed, change the blinking cursor by pressing the Y keyor toggle it by using the PREVIOUS or NEXT key. After the selections have been made tothe detectors and modules of both loops, press the ENTER key, at which time the panelwill reset.Observe the following protocol when using FlashScan devices:• FlashScan devices can be programmed to run in either CLIP or FlashScan mode• FlashScan devices cannot be mixed with CLIP devices on the same loop, unless theentire loop is programmed for CLIP mode• FlashScan programmed detectors cannot be used with CLIP modules on the sameloopThe following table lists the available FlashScan devices:7DEOH )ODVK6FDQ 'HYLFHVType NotifierION FSI-751Photo FSP-751Photo/Thermal FSP-751TDuct Detector FSD-751Laser Detector FSL-751Multi Detector FSM-751Thermal FST-751Thermal R-O-R FST-751RMonitor Module FMM-1Micro Monitor Module (for pullstation replacement)FSM-1Mini Module FMM-1012-Wire Detector Monitor Module FZM-1Control Module - NAC FCM-1Control Module - Relay FRM-1&3URJUDP &KDQJHSDVVZRUG&)WR H[LW)/$6+6&$1 /'(7 /02' /'(7 /02'1 1 1 1Technical Manuals Online! - http://www.tech-man.com