$SSHQGL[ $ 5HOHDVLQJ $SSOLFDWLRQV How to Program a Releasing Zone46 AFC-600 Programming PN 51032:A 3/8/99+RZWR3URJUDPD5HOHDVLQJ=RQHThis section provides details for programming the releasing functions: Delay Timer,Abort Switch, Cross Zone, and Soak Timer.+RZWR3URJUDPD'HOD\7LPHUUse a Delay Timer to specify the elapsed time between alarm activation of an initiatingdevice and activation of all output devices mapped to that device. You can set the DelayTimer from 0 to 60 seconds. For example, Figure 58 shows graphical representation ofa 15-second timer:)LJXUH ([DPSOH RI 6HFRQG 'HOD\ 7LPHUTo program a Delay Timer, enter a 0-60 second value as shown in "R0-R9 (ReleasingFunctions)" on page 30.+RZWR3URJUDPDQ$ERUW6ZLWFK'HILQLWLRQ RI $ERUW6ZLWFKHVThe control panel provides four types of Abort Switches (ULI, IRI, NYC, and AHJ)that you can use, that will affect the operation of a Delay Timer mapped to the sameReleasing Zone. For example, an Abort Switch selected for Releasing Zone R05 onlyaffects the Delay Timer selected for R05. Other requirements for using an Abort Switchinclude the following:• Connecting an monitor module to a UL-listed abort station, such as the N-ARA-10shown in Figure 59.• Program the monitor module with the Type Code ABORT SWITCH . (Refer to “Howto Program a Monitor Module” on page 23).• Abort switch shall not be used with a preaction system.)LJXUH 1$5$ 8/OLVWHG $ERUW 6WDWLRQThis section contains information for programming each type of Abort Switch for aReleasing Zone.Continued on the next page...0153 04 501 53 045'HOD\ VHFRQGV$OO RXWSXWV5HOHDVLQJ =RQH 5,QLWLDWLQJ GHYLFH VLQ 5HOHDVLQJ =RQH5 DFWLYDWHV$ERUW 6ZLWFK0DQXDO $JHQW5HOHDVH OHYHUTechnical Manuals Online! - http://www.tech-man.com