Time Control Zones $SSHQGL[ % 6SHFLDO =RQH 2XWSXWVAFC-600 Programming PN 51032:A 3/8/99 717LPH&RQWURO=RQHV1RWH $OO DFWLYH 7LPH &RQWURORXWSXWV ZLOO WXUQ RII WHPSRUDULO\ZKLOH UHVHWWLQJ RU SURJUDPPLQJWKH FRQWURO SDQHOAll outputs with a CBE list containing F5 or F6 activate within the times specified forthe days of the week listed in F5 or F6. All smoke detectors with a CBE list containingF5 or F6 switch to their lowest sensitivity (AL:9) within the times specified for the daysof the week listed in ZF5 or ZF6. Refer to “Appendix C: AWACS Applications” onpage 73 for details on setting detector sensitivity.Time Control is active for all days of the week listed in F5 or F6. Holidays listed in F7are excluded unless you list Holidays (H) in the day-of-week selection of F5 and F6.Enter the time in a 24-hour format with the OFF time later than the ON time. Afterchanging programming using Time Control, always reset the control panel.&RGLQJ)XQFWLRQVIRU1$&6DQG3DQHO&LUFXLWVCoding Functions are pulsed signals that you can select, using Special Zone F8, toenergize NACs and Panel Circuits when a fire alarm activates. NACs and Panel Circuitswith a CBE list that includes F8 energize when activated by a fire alarm. Beforeselecting an output circuit for a two-stage Coding Function, note the following:• 1NAC and Panel Circuits activated exclusively by an initiating device with aHAZARD ALERT Type Code turn a steady even if selected for a Coding Function1RWH 'R QRW LQFOXGH ) LQ WKH&%( OLVW RI 1$&V DQG 3DQHO&LUFXLWV XVHG IRU UHOHDVLQJ RU]RQH FRGLQJ DSSOLFDWLRQV• 1The control panel automatically sends an Alert signal to any of the four NACsmapped to Z00 and F8, but not mapped to the alarm signal. After 5 minuteswithout an acknowledge or silence, the Alert signal becomes steady.Select Coding Functions on a global basis, through Special Zone F8. That is, all NACsand Panel Circuits selected for Coding Functions, will sound the same code whenactivated. Table 36 contains descriptions of each Coding Function selection:7DEOH &RGLQJ )XQFWLRQ 6HOHFWLRQVCoding FunctionSelection SignalMarch Time (default) 120 ppm (pulses per minute)Two-Stage 1 Alert signal – 20 PPM;general alarm signal: steady toneCalifornia 10 sec. On, 5 sec. Off, repeatsTemporal 0.5 on, 0.5 off, 0.5 on, 0.5 off, 0.5 on, 1.5 off, repeatsTechnical Manuals Online! - http://www.tech-man.com