1. Product Description Controls and Indicators12 AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002Controls and IndicatorsThe controls and indicators on the Main Circuit Board include: a membrane panel, five system statusLED indicators, the LCD display, and the local panel sounder.Membrane PanelMounted on the main circuit board, the membrane panel includes five system status LED indicators anda window for the LCD display. The membrane panel, which is visible with the cabinet door closed, has21 keys, including a 12 key alphanumeric pad similar to a telephone keypad.Figure 1 Membrane/Display PanelSystem Status LED IndicatorsSystem Status LED Indicators are provided to annunciate the following conditions:LCD DisplayThe control panel uses a 40-character (2 lines x 20 characters) high viewing angle LCD display with acharacter height of 3/16 inches. The display includes a long-life LED backlight that remainsilluminated. If AC power is lost and the system is not in alarm, the LED backlight will turn off toconserve batteries.Local SounderThe control panel has a local sounder to provide separate and distinct pulse rates for alarm, trouble, andsupervisory conditions.ï AC Power (green) ï Supervisory (yellow)ï Fire Alarm (red) ï Alarm Silence (yellow)ï System Trouble (yellow)Function keysAcknowledge/StepAlarm SilenceDrillSystem Reset (lamp test)Service/program keys:keys labeled 1 to 9* (detector) key# (module) key0 (recall) keyFour cursor keys (up, down,right and left/backspace)Enter keySystem Status LEDIndicatorsLCD DisplayMembrane Panel9200disp.cdrTechnical Manuals Online! - http://www.tech-man.com