1. Product Description Circuits14 AFP-100/AFP-100E Instruction PN 51010:C1 02/06/2002CircuitsShown below is a layout of the terminal blocks on the main circuit board and a breif description of whatis provided.Figure 3 Terminal LayoutSignaling Line Circuit (SLC)One SLC, configurable for NFPA Style 4, 6 or 7, is provided for communication to addressable monitor(initiating device) and control (output device) modules.Output CircuitsThe following output circuits are available on the FACP:ï 24 VDC Resettable Power Output 300 mAï 24 VDC Nonresettable Power Output 300 mAï 24 VDC Battery Charger (up to 18 AH batteries)Notification Appliance Circuits (NACs)Two NACs, configurable for Style Y (Class B) or Style Z (Class A), are provided with variousprogrammable features.RelaysThree dry contact relays are provided for System Alarm and System Trouble (Form-C contacts) andSupervisory (Form-A contacts). Contacts are rated 2.0 amps @ 30 VDC (resistive) and 0.5 amps @ 30VAC (resistive).24V UNREG 24V NONRS 24V RST BELL 2 POWER BELL 1 POWER SUPV ALARM TROUBLEB+ A+ A- B- B+ A+ A- B- NO C NO NC C NO NC C A B B+ A+ B- A-1 COMM 2ACS SHIELD SLC SLCOUT+ IN+ OUT- IN-TB4TB2TB1TB3TB7TB5TB624 VDC Power9200edge.cdrNACs Relays SLCTechnical Manuals Online! - http://www.tech-man.com