11 AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016Installation Installation Checklist3.2.1 Memory-Backup BatteryThe lithium battery on the CPU provides backupof the CPU’s on-board memory during power loss.The CPU ships with an insulator to prevent thebattery from discharging. To preserve the battery,the insulating tube should be left in place as longas possible before applying AC power.If the insulator is not removed before applying ACpower, the control panel will show a faultsituation.This battery’s shelf-life should exceed 10 years,but if for some reason it fails, the control panelwill show a fault when powered up. To replace the lithium battery:1. Make a full backup of all system settings to prevent loss of all programming data.2. Disconnect all power sources.3. Lift clip gently using a hardware tool or screwdriver, and remove battery from under clip (usefingers, as screwdriver could damage components) before inserting new battery.4. Follow system power-up procedures.5. Dispose of used battery promptly. Keep away from children. Do not disassemble and do notdispose of in fire.6. Install main power supply & batteries inseparate enclosure. Run cable to main& optional power supplies, DC poweroutputs, relays, etc.• Section 3.10 “Connecting Power Sources and Outputs”WARNING:DO NOT ACTIVATE POWER AT THIS TIME. DO NOT CONNECT BATTERIES. Main power supply. • NPS Installation Sheet Auxiliary power supply and/orexternal battery charger7. Check that all mounting holes are secured to insure a proper Earth Ground connection.8. Connect wire shielding to Earth Ground.9. Remove insulator from lithium batteryon CPUSection 3.2.1 “Memory-Backup Battery”10. Apply AC power to the control panel by placing the external circuit breaker to the ON position.Do NOT connect batteries until AC power is checked (see next step).11. Check AC power. Section 3.10.3 “Checking AC Power”12. Connect the batteries using interconnect cable as described in Section 3.10.2 “Connecting Local andRemotely Powered Devices”.13. Program the control panel. Programming Manual.Task Refer to:Table 3.1 Installation Checklist (2 of 2)!Lift clip gently whileremoving battery Dotted line indicateslocation of insulatorASM-02-056-Battery.wmf! CAUTION:THE BATTERY USED IN THIS DEVICE MAY PRESENT A RISK OF FIRE OR CHEMICAL BURNIF MISTREATED.DO NOT RECHARGE, DISASSEMBLE, HEAT ABOVE 100°C, OR INCINERATE.A REPLACEMENT CR2477 LITHIUM BATTERY CAN BE ORDERED FROM NOTIFIER BYQUOTING THE PART NUMBER FG-65-016. USE OF ANY OTHER BATTERY MAY PRESENT ARISK OF FIRE OR EXPLOSION.