AFP-3030 Installation Manual — P/N DOC-01-037:B 25/08/2016 4Specifications System Overview2.2 Specifications2.2.1 Supply Rating2.2.2 Environmental Specifications2.3 System ComponentsCentral Processing Unit (CPU) with Power Supply. The central processing unit for theAFP-3030 is a combination of the CPU and on board power supply (NPS-5CHS or NPS-11CHS).The power supply provides +24 V DC power and a battery charger for the basic system. Auxiliarypower supplies and/or battery chargers are available to customize large systems.Indicating Unit. The indicating unit acts as the primary display for the status of the Fire System.The ACM-ZM provides the status indications, with the AEM-ZM providing additional zonal indi-cations. The Indicating Unit also provides a Bulgin Switch for Trial Evacuation, a Bulgin Switchfor Silence, and a Door Switch.Keypad/Display. The keypad with built in LCD display serves as a secondary display for theAFP-3030.Enclosures. Five cabinet sizes are available; CAB650, CAB900, 18U, 28U, and 40U. Refer toSection 2.5, “System Cabinets”, on page 8 for additional information.SLC Loops: LCM-320, LEM-320 . To provide one SLC loop, connect one LCM-320 to thepanel. Connect an LEM-320 to the LCM-320 to provide a second loop. Up to five pairs of modulescan be installed on the panel to provide a maximum of ten SLC loops.Network Connection. Connect a wire or fibre version of the NCM or the HS-NCM to provide aconnection to the Noti•Fire•Net (network version 5.0 or higher) or High-Speed Noti•Fire•Net.Annunciators. The AFP-3030 supports ACM-24AT/ACM-48A (and their expanders) with either64 or 96 points at an address, as well as LDM-32 (and expanders) and Notifier’s other ACSdevices. (See Section 2.6 “Compatible Equipment” if looking for specific ACS devices.)Supply Rating Parameter DetailsInput Fuse Rating M205 Fuse - 250V, 8.0AInput Voltage Rating NPS-5CHS: 100-240 V AC, 50-60 Hz, 0.8-2.5 ANPS-11CHS: 100-240 V AC, 50-60 Hz, 1.5-5.0 AOutput Ratings DetailsOutput Current NPS-5CHS: 5.6 A * @ 27.3 V DCNPS-11CHS: 11.7 A* @ 27.3 V DC*A total of 15 A can be drawn from the panel, with the difference in current beingdrawn from the panel batteries.Output Ratings (Charger) DetailsCharger Voltage 27.3 V DCEnvironmental SpecificationsParameters DetailsEnvironmental Limits 0°C to 49°C dry heat40°C @ 93% relative humidityIP Rating CAB650, CAB900: IP3018U, 28U, 40U: IP52NOTE: Annunciators for the AFP-2800 operate on a different baud rate and are not compatiblewith the AFP-3030.